Galaxy Flex Installer Manual
Parameters [51]
87
Infinite Exit Time
Assign a value of 000 seconds to set the Exit Time to infinity. An Exit terminator activation
(Final or Push-set zone) is required to complete the setting of the system. The infinite Exit
Time is normally used with a Push-set zone to terminate the setting and an Entry zone to
start the unsetting procedure.
Note:
If the system is programmed to Autoset and the Exit Time is programmed to 000,
the Exit Time is set to 60 seconds for the Autoset. There is no requirement for a
Push-Set zone to be activated.
Setting Multiple Groups
You can assign a different value to each group. If more than one is group is being set, the
longest exit time is adopted for all groups. Night exit uses a common exit time for all
groups.
Entry Time [51.05]
This parameter determines the entry time allowed to users when unsetting the system.
The default time is 45 seconds and the range is 0 to 300 seconds. Use 000 seconds to set the
Entry Time to infinity.
You can assign a different value to each group.
Note:
A
assigned to a Final zone doubles the programmed Entry Time of the group to
which it is allocated.
System Reset [51.06]
Use this option to select the user type that can reset the system following an intruder alarm.
A remote code can also change this option. The default type is 3 and the range is:
3 to 5 for the user.
6 for the manager.
7 for the engineer.
You can assign a different value to each group.
Note:
This option is affected by
Reduced Resets
[
51.55.3]
.
The panel only requests Engineer Level Reset if alarms have been signalled via the
Communication Module and appropriate type reset is set to 7. If no signal is transmitted, the
reset is automatically reduced to type 6. This feature is only active when the DTMF
signalling format is selected.
Note:
This option can also be programmed using
Reset Levels [51.65]
.
Tamper Reset [51.07]
Use this option to select the user type that can reset the system following a tamper. A remote
code can also change this option. The default type is 3 and the range is:
3 to 5 for the user.