Galaxy Flex Installer Manual
Install peripheral devices
25
Figure 10 Power cable spans for two camera PIRs
L1 is the distance from the Power Supply to the first camera PIR
L2 is the distance between the first and second camera PIR
Connection to the RS485 bus
Note:
Do not connect cameras or an Ethernet module to this bus.
1.
Before applying power, select a valid and unique address on each device. The address
on most devices is set by either jumpers or a rotary switch. Note that a Keyprox will
assume the address of both a keypad and a MAX reader. Care must be taken not to
duplicate addresses when a MAX reader and Keyprox are both installed
Peripheral
Valid addresses
Mk8 Keypad
0-7
Mk8 Keyprox
0-7
TouchCenter
0-2
RIO/PSU
2-12
DCM Reader
0-3
MAX
0-7
RF Portal
0-15
2.
Connect an RS485 data cable between the panel and each device in a daisy-chain
configuration, using the information in the tables below
Panel Peripherals
+12 V
+ V in
0 V
–
A
A
B
B