GEK-113285A
G650 Generator Protection & Control System
5-73
5 SETTINGS
5.4 PROTECTION ELEMENTS
5
We would obtain a mixed Protection Between figure (d) and figure (e).
b) SETTINGS
Table 5–74: 32 ELEMENT SETTINGS
The snapshot event setting enables or disables the snapshot event generation for this element.
Function:
Enables or disables the directional element.
Blk Time After Close:
In seconds. This settings allow to block the element 32 during the time specified in the
setting after the breaker switches from OPEN to CLOSED.
Dir Power Angle (1-2) (RCA):
This setting specifies the relay characteristic angle (RCA) for the directional power
element. This setting provides ability to respond to the function in any direction defined
(active forward power, active low forward power, etc.)
SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Block from off-line
Blk Time After Close
0.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 1 (RCA1)
Dir Power Angle 1
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 1
Stage 1 Tap
10.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 1
Stage 1 Time
60.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 2 (RCA2)
Dir Power Angle 2
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 2
Stage 2 Tap
20.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 2
Stage 2 Time
60.00
0.01 s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...