D-4
G650 Generator Protection & Control System
GEK-113285A
D.4 IEC 104 SETTINGS
APPENDIX D
D
D.4IEC 104 SETTINGS
The Communication settings for IEC 60870-5-104 protocol are the following:
Function:
Enable or disable the protocol operation.
TCP Port:
Listening TCP port in the relay. Default value is 2404.
Common Addr of ASDU:
Address in the ASDU header. Default value is 255.
Cyclic Meter Period:
Number of seconds for instantaneous meterings. 0 means no spontaneous
meterings.
Synchronization event:
Not implemented.
The G650 relay has a custom Binary Inputs points list, called User Map; it is common for any protocol. In the case of IEC
104 Protocol, those points are GROUP1 and GROUP2.
The IEC 104 User Map can be configured using the
EnerVista 650 Setup
software in
Setpoint>Relay Configuration-
>Control Events.
The User Map contains 128 Binary Inputs. To each point of the User Map, the user can assign any of the
binary states of the G650 relay, also is possible to combine those states using OR and NOT functions. These states are:
contact inputs and outputs, virtual outputs, protection element states, PLC states, etc. The User Map always has a size of
128 Binary Inputs. Points in the User Map that are not configured will have a zero value in the answer.
It is possible to implement more complex logic than simple OR and NOT using the
PLC Editor
tool in
EnerVista 650 Setup
in the menu
Setpoint>Logic Configuration.
These complex signals (Virtual Outputs) can be assigned to the binary points
in the Control Events configuration for the IEC 104 user map.
PRODUCT SETUP>COMMUNICATION SETTINGS >IEC 870-5-104
NAME
VALUE
UNITS
RANGE
Function
DISABLED
TCP Port
2404
[0 : 65535]
Common Addr of ASDU
255
[0 : 65535]
Cyclic Meter Period
0
[0 : 3600]
Synchronization Event
0
[0 : 3600]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...