GEK-113285A
G650 Generator Protection & Control System
A-1
APPENDIX A
A.1 LOGIC OPERANDS
A
APPENDIX A LOGIC OPERANDSA.1LOGIC OPERANDS
OPERANDS - G650 - MODEL FX - GX
INTERNAL SYSTEM STATUS
AUTOCHECK INTERNAL STATES (CRITICAL)
DSP Internal States (Critical to metering and
protection)
DSP COMM ERROR
DSP Communication Error: (0) Rignt communications
between DSP and main processor; (1) Communication
Error between DSP and main processor
MAGNETIC MODULE
ERROR
Magnetic Module Error: (0) Right Communication
between DSP and magnetic module processor; (1)
Communication Error between DSP and magnetic
module processor
CALIBRATION ERROR
Calibration Error: (0) Right calibration values stored; (1)
The calibration values stored are out of the calibration
limits.
Flash Internal States (Critical to Relay configuration
and stored data)
E2PROM STATUS
E2prom status :(0) Not configured or problems during
writing process ; (1) Configured and OK
IO Board States (Critical to operation and
protection)
BOARD F STATUS
Board F status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
BOARD G STATUS
Board G status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
BOARD H STATUS
Board H status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
BOARD J STATUS
Board J status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
IEC61850 INTERNAL STATES (NON CRITICAL)
OTHER INTERNAL STATES (NON CRITICAL)
Other internal states
USER MAP STATUS
User map status: (0) Not configured ; (1) Configured
FACTORY
CALIBRATION
Calibration status (0) Not calibrated ; (1) Relay calibrated
FLEXCURVE A STATUS User curve A: (0) Not configured (1) Configured
FLEXCURVE B STATUS User curve B: (0) Not configured (1) Configured
FLEXCURVE C STATUS User curve C: (0) Not configured (1) Configured
FLEXCURVE D STATUS User curve D: (0) Not configured (1) Configured
Green Zone
Memory internal status
Yellow Zone
Memory internal status
Orange Zone
Memory internal status
Red Zone
Memory internal status
UpTime
System Time
Autocheck Internal States (Not available)
TIMER STATUS
Real time clock autocheck (not available)
GRAPHIC STATUS
Graphic display status (not available)
ALARM TEXT ARRAY
Text display status (not available)
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...