G650 Generator Protection & Control System
GEK-113285A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.1.6 NEUTRAL INSTANTANEOUS OVERCURRENT (50N)
2.4.1.7 SENSITIVE GROUND INSTANTANEOUS OVERCURRENT (50SG)
2.4.1.8 NEGATIVE SEQUENCE TIME OVERCURRENT (51-2)
Current Input
Fundamental Phasor (without harmonics)
Pickup level
0.05 to 160.00 A in steps of 0.01 A
Dropout level
97% to 98% of the pickup level
Level Accuracy
Values at nominal frequency:
±
0.5% of the reading
±
10 mA from 0.05 to 10 A
±
1.5% of the reading for higher values
Overreach
< 2%
Trip delay
0.00 to 900.00 s. in steps of 0.01 s.
Reset delay
0.00 to 900.00 s. in steps of 0.01 s.
Operate time
<50 ms at 3 x Pickup at 50 Hz, typically
Timing accuracy
at 0 ms time delay (no intentional delay): 50ms
at non-zero time delay:
±
3% of operate time or 50 ms
(whichever is greater)
Snapshot Events
Selectable by setting
Current Input
Phasor (without harmonics) or RMS
Rated current
For connection to 1 or 5 A CTs.
Pickup level
0.005 to 16.000 A in steps of 0.001 A
Dropout level
97% to 98% of the pickup level
Level Accuracy
Values at nominal frequency:
±
1.5% of the reading
±
1 mA from 0.005 to 16 A
Overreach
< 2%
Trip delay
0.00 to 900.00 s. in steps of 0.01 s.
Reset delay
0.00 to 900.00 s. in steps of 0.01 s.
Operate time
<50 ms at 3 x Pickup at 50 Hz, typically
Timing accuracy
at 0 ms time delay (no intentional delay): 50ms
at non-zero time delay:
±
3% of operate time or 50 ms
(whichever is greater)
Snapshot Events
Selectable by setting
Current Input
Fundamental Phasor (without harmonics)
Pickup level
0.05 to 160.0 A in steps of 0.01 A
Dropout level
97% to 98% of the pickup level
Level Accuracy
Values at nominal frequency:
±
0.5% of the reading
±
10 mA from 0.05 to 10 A
±
1.5% of the reading for higher values
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...