GEK-113285A
G650 Generator Protection & Control System
5-81
5 SETTINGS
5.5 CONTROL ELEMENTS
5
5.5.4.3 SETTINGS
Setpoint > Control Elements > Synchrocheck
There is only one synchrocheck element in the G650.
Table 5–81: 25 ELEMENT SETTINGS
Settings description for element 25:
Function permission (Function):
This setting allows enabling and disabling the synchrocheck element.
Voltage Level determination settings for busbar and line:
This setting group allows determining the voltage levels considered as dead and live for line and busbar voltage.
Dead Bus voltage level (Dead Bus Level):
Voltage level considered as dead bus
Live Bus voltage level (Live Bus Level):
Voltage level considered as live bus
Dead Line voltage level (Dead Line Level):
Voltage level considered as dead line
Live Line voltage level (Live Line Level):
Voltage level considered as live line
Synchrocheck settings (live bus, live line):
G650 relays verify synchronism by establishing and comparing three basic parameters: the difference in module and angle
of voltage phasors, and the frequency slip of a phasor related to the other one. synchrocheck settings include a fourth time
setting, that allows using an anticipative algorithm to issue a closing signal.
Voltage Difference (Max Volt Difference):
Maximum Difference in module between the line and busbar
voltage to allow a closing in the synchrocheck element.
Angle Difference (Max Angle Difference):
Maximum Difference in angle between the line and busbar
voltage to allow a closing in the synchrocheck element.
Frequency Slip (Max Freq Difference):
Maximum difference in frequency (slip) between both voltage
values to be compared in the synchrocheck element.
Breaker Closing time (Time):
Estimated breaker Closing time, used for establishing the
Closing order in a moment that allows the busbar and line
voltages to be in phase.
SETPOINT > CONTROL ELEMENTS > SYNCHROCHECK
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Dead bus voltage level
Dead Bus Level
10.00
0.01 V
[0.00 : 500.00]
Live bus voltage level
Live Bus Level
50.00
0.01 V
[0.00 : 500.00]
Dead line voltage level
Dead Line Level
10.00
0.01 V
[0.00 : 500.00]
Live line voltage level
Live Line Level
50.00
0.01 V
[0.00 : 500.00]
Voltage Difference
Max Volt Difference
10.00
0.01 V
[2.00 : 500.00]
Angle Difference
Max Angle Difference
10.0
0.1 Deg [2.0 : 80.0]
Frequency Slip
Max Freq Difference
20
10 mHz [10 : 5000]
Breaker Closing time
Time
0.50
0.01 s
[0.01 : 600.00]
Dead Line – Dead Bus Function permission
DL-DB Function
DISABLED
N/A
[DISABLED – ENABLED]
Live Line – Dead Bus Function permission
LL-DB Function
DISABLED
N/A
[DISABLED – ENABLED]
Dead Line – Live Bus Function permission
DL-LB Function
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...