GEK-113285A
G650 Generator Protection & Control System
C-7
APPENDIX C
C.3 IMPLEMENTATION TABLE
C
C.3IMPLEMENTATION TABLE
The following table shows objects, variations, function codes and qualifiers supported by G650 units, both in requests and
responses for DNP3 protocol. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07 or 08, will
be responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers
17 or 28. For change-event objects, qualifiers 17 or 28 are always responded.
Text in
bold and italic
indicates functionality higher than DNP3 implementation level 2.
a) IMPLEMENTATION TABLE (SHEET 1 OUT OF 3)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28,
respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01
(for change-event objects, qualifiers 17 or 28 are always responded).
Note 3: Cold restarts are implemented the same as warm restarts – The G650 is not restarted, but the DNP process is restarted.
OBJECT
REQUEST
RESPONSE
Object
No.
Variation
No.
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function Codes
Qualifier Codes
(hex)
1
0
Binary Input (Variation 0 is used to
request default variation)
1 (read)
22 (assign class)
06 (no range, or all)
00,01 (start-stop)
07,08 (limited qty)
17,28 (index)
1
1
Binary Input
1 (read)
22 (assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-stop)
17,28
(index)
See Note 2
1
2
Binary Input with Status
(default – see Note 1)
1 (read)
22 (assign class)
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-stop)
17,28
(index)
See Note 2
2
0
Binary Input Change - All Variations
See Note 1
1 (read)
06
(no range, or all)
07,08
(limited qty)
2
1
Binary Input Change without Time
1 (read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol. resp.)
17, 28
(index)
2
2
Binary Input Change with Time
1 (read)
06
(no range, or all)
07,08
(limited qty)
129
(response)
130
(unsol. resp.)
17, 28
(index)
10
0
Binary Output - All Variations
1 (read)
06
(no range, or all)
00,01
(start-stop)
07,08
(limited qty)
17,28
(index)
10
2
Binary Output Status
See Note 1
1 read
00,01
(start-stop)
06
(no range, or all)
07,08
(limited qty)
17,28
(index)
129
(response)
00, 01
(start-stop)
17,28
(index)
See Note 2
12
1
Control Relay Output Block
3
(select)
4
(operate)
5
(direct op)
6
(dir.op, noack)
00,01
(start-stop)
07,08
(limited qty)
17, 28
(index)
129
(response)
echo of request
20
0
Binary Counter - All Variations
1
(select)
7
(freeze)
8
(freeze noack)
9
(freeze clear)
10
(frz.cl. noack)
06
(no range, or all)
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...