C-2
G650 Generator Protection & Control System
GEK-113285A
C.1 DNP 3.0 PROTOCOL SETTINGS
APPENDIX C
C
1.
Physical Port
: The G650 supports the Distributed Network Protocol (DNP) version 3.0. The G650 can be used as
a DNP slave device connected up to three DNP masters (usually RTUs or SCADA master stations). The Physical
Port setting is used to select the communications port assigned to the DNP protocol for a specific logical DNP slave
device of G650. When this setting is set to NETWORK, the DNP protocol can be used over either TCP/IP or UDP/
IP.
2. Address
: This setting is the DNP slave address. This number identifies de G650 on a DNP communications link.
Each logical DNP slave should be assigned a unique address.
3-22.
IP Addr Client x Oct x:
this setting is one of four octets of an IP address. The G650 relay can respond to a
maximum of 5 specific DNP masters (not in the same time). To set the IP address of DNP master it is necessary to
set four octets (e.g. to set the IP address of the first DNP master to 192.168.48.125, you should set
IP Addr Client1
Oct1
= 192,
IP Addr Client1 Oct2
= 168,
IP Addr Client1 Oct3
= 48,
IP Addr Client1 Oct4
= 125).
23.
TCP/UDP Port
: TCP/UDP port number for the case of DNP3 communication being performed through the
Ethernet.
24.
Unsol Resp Function
: ENABLED, if unsolicited responses are allowed, and DISABLED otherwise.
25.
Unsol Resp TimeOut
: sets the time the G650 waits for a DNP master to confirm an unsolicited response.
26.
Unsol Resp Max Ret
: This setting determines the number of times the G650 will retransmit an unsolicited
response without receiving a confirmation from the master. Once this limit has been exceeded, the unsolicited
response will continue to be sent at larger interval. This interval is called unsolicited offline interval and is fixed at 10
minutes.
27.
Unsol Resp Dest Adr
: This setting is DNP address to which all unsolicited responses are sent. The IP address to
which unsolicited responses are sent is determined by the G650 from either the current DNP TCP connection or the
most recent UDP message.
28-32. Scale Factor
: These settings are numbers used to scale Analog Input point values. These settings group the G650
Analog Input data into types: current, voltage, power, energy, and other. Each setting represents the scale factor for
all Analog Input points of that type. For example, if the
Voltage Scale Factor
is set to a value of 1000, all DNP
Analog Input points that are voltages will be returned with the values 1000 times smaller (e.g. a value 72000 V on
the G650 will be returned as 72). These settings are useful when Analog Input values must be adjusted to fit within
certain ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (i.e. the value will be
10 times larger).
33-37. Deadband
: These settings are the values used by the G650 to determine when to trigger unsolicited responses
containing Analog Input data. These settings group the G650 Analog Input data into types: current, voltage, power,
energy, and other. Each setting represents the default deadband value for all Analog Input points of that type. For
example, in order to trigger unsolicited responses from the G650 when any current values change by 15 A, the
Current Deadband
setting should be set to 15. Note that these settings are the default values of the deadbands.
DNP object 34 points can be used to change deadband values, from the default, for each individual DNP Analog
Input point. Whenever power is removed and re-applied to the G650, the default deadbands will be in effect.
38.
Msg Fragment Size
: This setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer
confirmations to be necessary which can provide for more robust data transfer over noisy communication channels
SETTING NO
SETTING NAME
DEFAULT VALUE
RANGE
40
Binary Input Block2
CTL EVENTS 17-32
See the explanation below
41
Binary Input Block3
CTL EVENTS 33-48
See the explanation below
42
Binary Input Block4
CTL EVENTS 49-64
See the explanation below
43
Binary Input Block5
CTL EVENTS 65-80
See the explanation below
44
Binary Input Block6
CTL EVENTS 81-96
See the explanation below
45
Binary Input Block7
CTL EVENTS 97-112
See the explanation below
46
Binary Input Block8
CTL EVENTS 113-128
See the explanation below
47
Binary Input Block9
SWITCHGEAR 1-8
See the explanation below
48
Binary Input Block10
SWITCHGEAR 9-16
See the explanation below
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...