GEK-113285A
G650 Generator Protection & Control System
F-15
APPENDIX F
F.1 FACTORY DEFAULT SETTINGS
F
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
50.50
0.01 Hz
[20.00 : 65.00]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Minimum voltage threshold
Minimum Voltage
30
1 V
[30 : 500]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > SYNCHROCHECK
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Dead bus voltage level
Dead Bus Level
10.00
0.01 V
[0.00 : 500.00]
Live bus voltage level
Live Bus Level
50.00
0.01 V
[0.00 : 500.00]
Dead line voltage level
Dead Line Level
10.00
0.01 V
[0.00 : 500.00]
Live line voltage level
Live Line Level
50.00
0.01 V
[0.00 : 500.00]
Voltage Difference
Max Volt Difference
10.00
0.01 V
[2.00 : 500.00]
Angle Difference
Max Angle Difference 10.0
0.1 Deg
[2.0 : 80.0]
Frequency Slip
Max Freq Difference
20
10 mHz
[10 : 5000]
Breaker Closing time
Time
0.50
0.01 s
[0.01 : 600.00]
Dead Line – Dead Bus Function
permission
DL-DB Function
DISABLED
N/A
[DISABLED – ENABLED]
Live Line – Dead Bus Function
permission
LL-DB Function
DISABLED
N/A
[DISABLED – ENABLED]
Dead Line – Live Bus Function
permission
DL-LB Function
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...