5-128
G650 Generator Protection & Control System
GEK-113285A
5.8 RELAY CONFIGURATION
5 SETTINGS
5
5.8.3.1 HOW TO PROGRAM AN OPERATION
Example of how to program an operation to close a breaker with an operating time of 90 ms (closing), incorporating 52/b
contacts to indicate the change of position, using an interlock logic to enable the operation if there is no autoreclose in
progress. The operation must be commanded from the relay faceplate using one of the available operation push buttons.
To configure the related operation, go to
Setpoint > Relay Configuration
and select
Operations
tab.
This screen shows all the fields required for the operations configuration in the G650. In order to select an operation, press
on the operation name under the
Select
column, and all the related parameters will be enabled. The chosen name for the
operation is entered in “
Command Text
”. To configure an interlock logic, select the
Logic
option in “
Interlocks Type
”.
Once this option has been selected, the interlock configuration screen will be enabled. To display this screen, click on
“
Press for Logic
” for the desired operation on its
Interlocks
column. On this
Interlocks
screen, the two conditions that
conform the Interlock that enables the operation have been selected. To save the interlock, press on the disk icon on the
toolbar. A “
Logic Saved
” message will be displayed.
Once the Interlocks have been defined, the user must define the success conditions for the operation, define
Final State
Type
as LOGIC, and a “PRESS FOR LOGIC” message will light up below
Final States
. When clicking on “PRESS FOR
LOGIC”, the success condition screen will be displayed, defining there as BREAKER CLOSED.
The front key to be used for executing the Operation can be selected on the Frontal Key column, in this example the
Key I
option is selected on “
Frontal Key
”. As none of the other contact input or virtual output options are going to be used they
will be set as
None
. The success condition time “
Time out
” is set to
500 ms
, and the operation is only enabled through the
relay keypad, so only the
MMI
option is selected, thus disabling the rest of options (COM1, COM2, ETHERNET master are
not selected).
All the selections previously related are summarized in the following table:
Table 5–110: OPERATION SETTINGS
Finally, configure a contact output to be activated with the programmed Operation (Operation1).
OPERATION
COMMAND TEXT
SETTINGS
VALUE/SOURCE
Operation1
CLOSE BREAKER
INTERLOCK (LOGIC)
FINAL STATES (LOGIC)
BREAKER CLOSED
FRONT KEY
I Key
INPUT
Not configured
VIRTUAL OUTPUT
Not configured
TIMEOUT
500
CHANNELS
MMI
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...