APPENDIX C
C.1 DNP 3.0 PROTOCOL SETTINGS
C
39-48. Binary Input Block x
: These settings allow customization and change of the size of DNP Binary Inputs point list.
The default Binary Inputs point list contains 160 points representing binary states that are configured using
“
Setpoint->Relay Configuration
” menu from the EnerVista 650 Setup program. These 160 binary states are
grouped in 10 blocks of 16 points each. There are 128 bits (8 blocks of 16) called
Control Events
and 32 bits (2
blocks of 16) corresponding to the states of 16
switchgears
available in G650 relay. If not all of the 160 points are
required in the DNP master, a custom Binary Inputs point list can be created by selecting up to 10 blocks of 16
points. Each block represents 16 Binary Input points. Block 1 represents Binary Input points 0-15, block 2
represents Binary Input points 16- 31, block 3 represents Binary Input points 32-47, etc. The minimum number of
Binary Input points that can be selected is 16 (1 block). If all of the
Binary Input Block x
settings are set to “NOT
USED”, the default list of 160 points will be in effect. The G650 will form the Binary Inputs points list from the
Binary
Input Block x
settings up to the first occurrence of a setting value “NOT USED”. Permitted values for these settings
are: NOT USED, CTL EVENTS 1-16, CTL EVENTS 17-32, CTL EVENTS 33-48, CTL EVENTS 49-64, CTL
EVENTS 65-80, CTL EVENTS 81-96, CTL EVENTS 97-112, CTL EVENTS 113-128, SWITCHGEAR 1-8,
SWITCHGEAR 9-16.
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...