5-28
G650 Generator Protection & Control System
GEK-113285A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
The distribution of protection elements in tabled groups is described in Table 5–27:
Table 5–27: DISTRIBUTION OF PROTECTION AND CONTROL ELEMENTS
The settings used for setting table management are located in
Setpoint >Control Elements > Setting Group
:
Table 5–28: SETTING GROUP SETTINGS
Setting Group settings are as follows:
DEVICE NUMBER FUNCTION
TABLE 1
TABLE 2
TABLE 3
24 Volt/Hertz
(only enhanced model)
1x24
1x24
1x24
25 Synchronism Check (No group concept)
NA
NA
NA
27P Phase Undervoltage
1x27P
1x27P
1x27P
27X Auxiliary Undervoltage
1x27X
1x27X
1x27X
32DIR Directional Power
1x32
1x32
1x32
40 Loss of Excitation
1x40
1x40
1x40
46 Generator Unbalance
1x46
1x46
1x46
47 Negative Sequence Overvoltage
1x47
1x47
1x47
49S Generator thermal model
1x49S
1x49S
1x49S
50/27 Inadvertent Generator Energization
1x50/27
1x50/27
1x50/27
50-2 Negative Sequence IOC/
1x50-2
1x50-2
1x50-2
50BF Breaker Failure
(only enhanced model)
NA
NA
NA
50G Ground Instantaneous Overcurrent (measured from 4
th
current transformer)
1x50G
1x50G
1x50G
50N Neutral Instantaneous Overcurrent (calculated from the phase currents)
1x50N
1x50N
1x50N
50P Phase Instantaneous Overcurrent
1x50P
1x50P
1x50P
50SG Sensitive Ground IOC
(only enhanced model)
1x50SG
1x50SG
1x50SG
51-2 Negative Sequence TOC
1x51-2
1x51-2
1x51-2
51G Ground Time Overcurrent (measured from 4
th
current transformer)
1x51G
1x51G
1x51G
51N Neutral Time Overcurrent (calculated from the phase currents)
1x51N
1x51N
1x51N
51P/V Voltage Restraint Overcurrent High
1x51PH
1x51PH
1x51PH
51P/V Voltage Restraint Overcurrent Low
1x51PL
1x51PL
1x51PL
51SG Sensitive Ground TOC
(only enhanced model)
1x51SG
1x51SG
1x51SG
55 Power Factor Limiting
(only enhanced model)
1x55
1x55
1x55
59G Ground Overvoltage
1x59G
1x59G
1x59G
59N Neutral Overvoltage
1x59N
1x59N
1x59N
59P Phase Overvoltage
1x59P
1x59P
1x59P
59X Auxiliary Overvoltage
1x59X
1x59X
1x59X
67G Ground Directional
1x67G
1x67G
1x67G
67N Neutral directional
1x67N
1x67N
1x67N
78V Loss of mains
(only enhanced model)
1x78V
1x78V
1x78V
81O Overfrequency
1x810
1x810
1x810
81U Underfrequency
1x81U
1x81U
1x81U
81R Frequency Rate of Change
1x81R
1x81R
1x81R
87G Restricted Ground Fault
(only enhanced model)
1x87G
1x87G
1x87G
VTFF VT Fuse Failure
(only enhanced model)
(No group concept)
NA
NA
NA
Pulse Counters (No group concept)
NA
NA
NA
Analog Comparators (No group concept)
NA
NA
NA
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
Setting Description
Name
Default Value Step
Range
Setting Grouping Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Active Group
Active Group
GROUP 1
N/A
[GROUP 1 – GROUP 2 – GROUP 3]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...