B-106
G650 Generator Protection & Control System
GEK-113285A
B.7 MEMORY MAP
APPENDIX B
B
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 3 - Phase TOC Low 3 Settings(cont.)
1=ENABLED
0x32E8
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x32FB
Confirmation
address
W
1
Ajustes Aparamenta (16 elementos) - Switchgear Settings (16 items)
0x32FC
CONTACTS TYPE_01
F012
1
R/W
1
0=52a + 52b
1=52a
2=52b
3=NONE
0x32FD
CONTACTS TYPE_02
F012
1
R/W
1
0=52a + 52b
1=52a
2=52b
3=NONE
...
...
...
...
...
...
...
...
0x330B
CONTACTS TYPE_16
F012
1
R/W
1
0=52a + 52b
1=52a
2=52b
3=NONE
0x330C
FAIL TO OPEN 01 t
F004
1
R/W
1
[0 , 30000] ms
0x330D
FAIL TO OPEN 02 t
F004
1
R/W
1
[0 , 30000] ms
...
...
...
...
...
...
...
...
0x331B
FAIL TO OPEN 16 t
F004
1
R/W
1
[0 , 30000] ms
0x331C
FAIL TO CLOSE 01 t
F004
1
R/W
1
[0 , 30000] ms
0x331D
FAIL TO CLOSE 02 t
F004
1
R/W
1
[0 , 30000] ms
...
...
...
...
...
...
...
...
0x332B
FAIL TO CLOSE 16 t
F004
1
R/W
1
[0 , 30000] ms
0x332C
Snapshot Events SWGR 1
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x332D
Snapshot Events SWGR 2
F012
1
R/W
1
0=DISABLED
1=ENABLED
...
...
...
...
...
...
...
...
0x333B
Snapshot Events SWGR 16
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x334C
Confirmation address
W
1
Ajustes Interruptor - Breaker Settings
0x334D
Number of Switchgear
F004
1
R/W
1
[1 , 16]
0x334E
Maximum KI2t
F003
1
R/W
2
[0.00 , 9999.99] (KA)2 s
0x3350
KI2t Integ. Time
F003
1
R/W
2
[0.03 , 0.25] s
0x3352
Maximum Openings
F004
1
R/W
1
[0 , 9999]
0x3353
Max.Openings 1 hour
F004
1
R/W
1
[1 , 60]
0x3354
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x3367
Confirmation
address
W
1
Ajustes Contadores Interruptor - Breaker Maintenance Settings
0x3368
KI2t BKR Ph A Cnt
F003
1
R/W
2
[0.00 , 9999.99] (KA)2 s
0x336A
KI2t BKR Ph B Cnt
F003
1
R/W
2
[0.00 , 9999.99] (KA)2 s
0x336C
KI2t BKR Ph C Cnt
F003
1
R/W
2
[0.00 , 9999.99] (KA)2 s
0x336E
BKR Openings Cnt
F004
1
R/W
1
[0 , 9999]
0x336F
BKR Closings Cnt
F004
1
R/W
1
[0 , 9999]
0x3383
Confirmation
address
W
1
ADDRESS BIT
NAME
FORMAT
STEP MODE LENGTH
MISCELLANEOUS
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...