10-2
G650 Generator Protection & Control System
GEK-113285A
10.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
10 APPLICATION EXAMPLES
10
Press ESC key once.
Move rotating knob counterclockwise to
General Settings
and press it down.
General Settings 0
will be displayed now.
Press rotating knob down again.
Set ModBus Port Number to 502 and press rotating knob down.
Move counterclockwise the rotating knob to find ModBus Address COM1 and press it down.
Set ModBus Address COM1 to 254 with the rotating knob and then press it down.
Move clockwise the rotating knob to find
Press Intro to End
and press it down to validate the setting.
Connect a crossover 10/100 MB Ethernet cable from PC to the relay.
Open the EnerVista 650 SETUP program in the PC and under
Communication
⇓
Computer
menu and set:
IP Address
192.168.37.125
Port
502
Unit Identifier
254
Control Type to
ModBus/TCP
Startup Mode to
Communicate with relay
Click
ON
key.
The program will start connection with the relay showing the progress screen.
SEQUENCE
ACTION
SETTING
ACTION
----
IP Address OCT 1
Set to 192 with rotating knob and press it down
Move rotating knob clockwise
IP Address OCT 2
Set to 168 with rotating knob and press it down
Move rotating knob clockwise
IP Address OCT 3
Set to 37 with rotating knob and press it down
Move rotating knob clockwise
IP Address OCT 4
Set to 125 with rotating knob and press it down
Move rotating knob clockwise
Netmask OCT 1
Set to 255 with rotating knob and press it down
Move rotating knob clockwise
Netmask OCT 2
Set to 255 with rotating knob and press it down
Move rotating knob clockwise
Netmask OCT 3
Set to 255 with rotating knob and press it down
Move rotating knob clockwise
Netmask OCT 4
Set to 0 with rotating knob and press it down
Move rotating knob clockwise
Netway IP OCT 1
Leave default setting without any change
Move rotating knob clockwise
Netway IP OCT 2
Leave default setting without any change
Move rotating knob clockwise
Netway IP OCT 3
Leave default setting without any change
Move rotating knob clockwise
Netway IP OCT 4
Leave default setting without any change
Move rotating knob clockwise
Press INTRO
Press down the rotating knob to validate settings
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...