2.4.1.16 PHASE UNDERVOLTAGE (27P)
2.4.1.17 NEUTRAL OVERVOLTAGE (59NH)
2.4.1.18 GROUND OVERVOLTAGE (59G)
Voltage Input
Fundamental Phasor of phase-to-ground or phase-to-
phase voltages (selectable by setting)
Pickup level
3 to 500 in steps of 1 V
Dropout level
102% to 103% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Curve Shapes
Fixed time or inverse curve
Reset type
Instantaneous
Curve Multiplier (Time Dial)
0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Minimum Voltage Threshold
0 to 500 in steps of 1 V
Logic
Any/Two/All phases logic selectable by setting
Supervised by Breaker
Selectable by setting
Snapshot Events
Selectable by setting
Voltage Input
Fundamental Phasor of the neutral voltage (calculated
from phases)
Pickup level
3 to 500 in steps of 1 V
Dropout level
97% to 98% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Voltage Input
Fundamental Phasor of the ground voltage (measured
from 4th voltage transformer)
Pickup level
3 to 500 in steps of 1 V
Dropout level
97% to 98% of the pickup level
Level accuracy
±
1% reading
±
0.1% Full Scale from 10 to 500 V at
nominal frequency
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...