F-18
G650 Generator Protection & Control System
GEK-113285A
F.1 FACTORY DEFAULT SETTINGS
APPENDIX F
F
SETPOINT > CONTROL ELEMENTS > ACCIDENTAL ENERGIZATION
ACCIDENTAL ENERGIZATION 1 > ACCIDENTAL ENERGIZATION 2 > ACCIDENTAL ENERGIZATION 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Arming mode for Accidental
Energization
Accdnt Enrg Mode
UV AND OFF-LINE N/A
[UV AND OFF-LINE – UV
OR OFF-LINE]
Overcurrent Level to operate
Overcurrent pickup
1.50
0.01 A
[0.00 : 160.00]
Arming undervoltage value
Ph Undervoltage
pickup
40.00
0.01 V
[0.00 : 500.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...