1.4 650 HARDWARE
1 GETTING STARTED
1
without exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible to use
commercially available repeaters to increase the number of relays on a single channel to more than 32. Do not use other
connection configurations different to the recommended.
Lightening strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are internally provided. To ensure maximum reliability, all
equipment should have similar transient protection devices installed.
Figure 1–17: RS485 CONNECTION FOR 650 UNITS
To communicate through the G650 rear Ethernet port from a PC a crossover cable is required. If the connection is
performed through a hub or a switch, a direct Ethernet cable is required.
1.4.3 FACEPLATE DISPLAY
All messages are displayed on a 20x4 character LCD display. An optional graphic display is also available. Messages are
displayed in different languages according to selected model.
1.4.4 MAINTENANCE
G650 requires a minimum amount of maintenance when it is commissioned into service. G650 is a microprocessor based
relay and its characteristics do not change over time. As such no further functional tests are required. However, it is
recommended that maintenance on the G650 be scheduled with other system maintenance. The maintenance may involve
the following:
In-service maintenance:
1.
Visual verification of the analog values integrity such as voltage and current (in comparison to other devices on the
corresponding system).
2.
Visual verification of active alarms, relay display messages and LED indications.
3.
Visual inspection for any damage, corrosion, dust or loose wires.
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...