background image

www.mandik.com

MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: [email protected]

SEDM-D

Smoke extraction damper-multi

Technical Documentation

Installation, Commissioning, Operation, Maintenance and Service Manual

TPM 155/22

Version 2023-06-07

Содержание SEDM-D

Страница 1: ...267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mandik mandik cz SEDM D Smoke extraction damper multi Technical Documentation Installation Commissioning Operation Maintenance and Service M...

Страница 2: ...IMENSIONS 15 Technical parameters 16 V INSTALLATION 18 Placement and Installation 18 Statement of installations 19 Installation procedure 20 Cable connection 21 Shock absorber 22 Installation frame 22...

Страница 3: ...or The dampers consist of a single calcium silicate blade reinforced by steel crossbeams hanged on spring equipped hinges combined calcium silicate and aluminum frame a cold seal silicon gasket and a...

Страница 4: ...underpressure 1500 Pa overpressure 500 Pa Closed blade tightness class 3 according to EN 1751 Certificate of Constancy of Performance No 1391 CPR 2023 0030 Declaration of Performance No PM SEDM D 01...

Страница 5: ...perature and with a temperature range of 25 C to 50 C Connecting cables shall be guided from a pre punched hole in one of the corners of the damper frame to the junction box using delivered cable clip...

Страница 6: ...in accordance with NF 61 937 10 Hand operated rearming design with a magnet voltage of 48 V DC and with two end switches signaling of the damper blade position CLOSED STAND BY and OPEN SECURITY Electr...

Страница 7: ...esistance Insulation voltage open contact Cut off power DC Longevity cycles 0 5 A 0 1 Ohm 500 V 10 W 1000 Microswitch AC rating Microswitch degree of protection 230 V AC 5 A IP67 Compliance NF 61 937...

Страница 8: ...arming time at room temperature Longevity cycles Cycling period 40 s 30 s 300 min 120 s Maintenance maintenance free Compliance NF 61 937 1 NF 61 937 10 Rearming of the damper blade with electric moto...

Страница 9: ...amper should be used with a protection grille G1 G2 G3 or G4 Grille G1 is not powder painted as standard Can be powder painted if specified in the ordering key Grilles G2 G3 G4 are powder painted If n...

Страница 10: ...mm 12 mm 14 mm from the wall Detail A Section view 2 2 5 m m 4x Screw M5 for hanging the grille Grille G3 Design grille with thin louvers made from Al sheet no visible bolts easy to open and close 95...

Страница 11: ...test Continuous operation test at 20 C 70 C for 1 hour 5 hours Compliance NF 61 937 1 NF 61 937 10 End switches Type configuration G905 C NO NC Voltage 60 V DC Switchable DC current Contact resistanc...

Страница 12: ...O1 C End switch position open input 9 yellow FC O2 NO End switch position open normally open 10 green FC O3 NC End switch position open normally contact 11 blue FCB F1 C End switch position closed in...

Страница 13: ...ON the voltage of 24 V DC or 48 V DC respectively on MAG and MAG for at least 1 second to activate the damper To test the damper during the commissioning with the protection grille removed or open the...

Страница 14: ...e 7 Installing or closing and securing the protection grille For larger dampers it may be necessary to use both hands to rearm the damper and proceed in 7 steps Rearming electric motor design 1 Switch...

Страница 15: ...ing motor optional 6 Restraint mechanism 7 End switch module optional 8 Damper blade B H B H B 73 H 68 90 Dimensions without grille 80 built in depth Dimensions for mounting of grilles B 39 H 180 1 2...

Страница 16: ...85 0 1615 8 4 0 9 1 5 2 1 1 8 1 6 550 0 1610 8 4 0 9 1 6 2 3 1 9 1 6 400 0 1685 8 5 0 9 1 5 2 1 1 9 1 6 600 0 1767 9 0 9 1 7 2 5 2 1 7 450 0 1916 9 2 0 9 1 6 2 3 2 1 7 650 0 1924 9 5 1 1 9 2 6 2 1 1 7...

Страница 17: ...2 7 2 2 350 0 2079 9 4 1 1 7 2 3 2 2 1 8 650 0 3457 13 1 4 2 7 3 2 2 9 2 2 385 0 2311 10 4 1 1 1 9 2 5 2 3 1 9 700 0 3739 13 7 1 4 2 9 3 4 3 2 3 400 0 2411 10 7 1 1 2 2 5 2 4 1 9 750 0 4021 14 4 1 5...

Страница 18: ...r is built in the damper blade should not grind against the damper casing during opening or closing The distance between the damper and the construction must be 75 mm at the minimum according to EN 13...

Страница 19: ...nce class for the given pressure e g 40 mm PROMATECT L 500 45 mm THERMAX SL Tecniver 45 mm GEOTEC S 35 mm GEOFLAM F 35 mm GEOFLAM F Light Mortar or gypsum EI 90 ved i o S1500C300AAmulti 27 Mastic 27 I...

Страница 20: ...cable passage through the shaft wall and through the damper casing 10 Attach a shock absorber to the shaft wall or damper blade 11 Test opening and closing of the damper blade 12 Install a grille Inst...

Страница 21: ...special grommet through the shaft wall and the damper Connect the cable to the junction box and secure it to the cable clips with cable ties Secure the cable against pulling the end out of the juncti...

Страница 22: ...cements 5 Rubber seal 6 Promaseal Installation frame is delivered separately Shaft from concrete or aerated concrete Shaft from fire resistant panels Use a shock absorber that is delivered with the da...

Страница 23: ...to the opening and fix it with screws Screws 4x30 from the front side of the frame and screws 5x50 from the inner side Fill the gap between the frame and shaft with mastic mortar or gypsum Make sure t...

Страница 24: ...oke extraction damper SEDM D Page 24 Version 2023 06 07 TPM 155 22 5 Prepare SEDM D and set four fastening plates to the open position 6 Install SEDM D on the frame and mount it on four fastening plat...

Страница 25: ...oncrete With mastic mortar or gypsum B 10 H 10 70 Installation opening 1 Concrete or aerated concrete 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 S...

Страница 26: ...tion opening 1 Concrete or aerated concrete 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Installation frame installation procedure see page 23 5 Ins...

Страница 27: ...A 1 Fire resistant panels 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Screw 5x70 mm 4x connection of the damper with shaft X shaft wall thickness...

Страница 28: ...Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Installation frame installation procedure see page 23 5 Installation frame and damper fastening plate 4x X X 80 80 Detail A A B 20 5 Inst...

Страница 29: ...913 0 828 500 2 290 1 870 1 569 1 344 1 170 1 032 0 921 0 829 0 752 550 2 075 1 695 1 422 1 218 1 060 0 935 0 834 0 751 0 681 600 1 879 1 534 1 287 1 102 0 960 0 847 0 755 0 680 0 617 650 1 700 1 388...

Страница 30: ...dust free environment out of direct sunlight Ensure protection against moisture and extreme temperatures minumum temperature 5 C The dampers must be protected against mechanical and accidental damage...

Страница 31: ...to operation after assembly and after sequential revisions checks and functionality tests of all designs including operation of the electrical components must be successfully provided and finished Che...

Страница 32: ...g design with a magnet voltage of 24 V DC and with two end switches 24C2M Electric motor rearming design with a magnet voltage of 24 V DC and with two pairs of end switches 24C4M Electric motor rearmi...

Страница 33: ...th thin louvers with hidden bolts G4 design grille from drawn steel Grille colour RAL F SEDM D 500x500 Size B width x H height Accessories Grille Installation frame RESTRAINT MECHANISM SEDM D 24 V Spa...

Страница 34: ...m The producer reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mand...

Отзывы: