G650 Generator Protection & Control System
GEK-113285A
F.1 FACTORY DEFAULT SETTINGS
APPENDIX F
F
SETPOINT > CONTROL ELEMENTS > BREAKER FAILURE(ENHANCED MODELS ONLY)
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Supervision (retrip) pickup level
Supervision Pickup
1.00
0.01 A
[0.05 : 160.00]
Hiset pickup level
Hiset Pickup
5.00
0.01 A
[0.05 : 160.00]
Lowset pickup level
Lowset Pickup
2.00
0.01 A
[0.05 : 160.00]
Internal arc pickup level
Internal Arc Pickup
0.10
0.01 A
[0.05 : 160.00]
Internal arc time delay
Internal Arc Delay
10.00
0.01 s
[0.00 : 900.00]
Retrip time delay
Supervision Delay
10.00
0.01 s
[0.00 : 900.00]
Hiset time delay
HiSet Delay
10.00
0.01 s
[0.00 : 900.00]
Lowset time delay
LowSet Delay
10.00
0.01 s
[0.00 : 900.00]
Second stage time delay
2nd Step Delay
10.00
0.01 s
[0.00 : 900.00]
WITHOUT current element time delay No Current Delay
10.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE(ENHANCED MODELS ONLY)
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > FREQUENCY RATE OF CHANGE
FREQUENCY RATE OF CHANGE 1 > FREQUENCY RATE OF CHANGE 2 > FREQUENCY RATE OF CHANGE 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Direction of the frequency change
Freq. Rate Trend
INCREASING
N/A
[INCREASING -
DECREASING - BI-
DIRECTIONAL]
Operation Value in Hz/s
Freq. Rate Pickup
0.50
0.01 Hz/s
[0.10 : 10.00]
Minimum required voltage in %
nominal voltage
Freq. Rate OV Supv
40.00
0.01%
[0.00 : 110.00]
Minimum Frequency Threshold
Freq. Rate Min
45.00
0.01 Hz
[20.00 : 80.00]
Maximum Frequency Threshold
Freq. Rate Max
65.00
0.01 Hz
[20.00 : 80.00]
Frequency rate Trip Delay
Freq. Rate Delay
0.00
0.01 s
[0.00 : 60.00]
Snapshot Events Generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > LOSS OF MAINS(ENHANCED MODELS ONLY
LOSS OF MAINS 1 > LOSS OF MAINS 2 > LOSS OF MAINS 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Any phase or three phase
displacement mode to operate
Loss of Mains Mode
ONE PHASE
N/A
[ONE PHASE ]
Minimum Phase shift angle value to
operate
Phase Shift Angle
1.00
0.01 Deg
[2.00 : 22.00]
Minimum voltage threshold
Minimum Voltage
70
1 V
[30 : 500]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > LOSS OF EXCITATION
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...