GEK-113285A
G650 Generator Protection & Control System
C-21
APPENDIX C
C.8 ANALOG INPUTS
C
The "Fault Type" is represented by enumeration value. The table below shows values with DNP3 setting "Other Scale
Factor = 1".
If this setting has another value then "Enum Value" will be scaled by the adjusted factor.
For example if "Other Scale Factor = 0.001", then the value corresponding to "TRIPH" fault type will be 2000.
NAF indicates that the type of fault has not been calculated.
POINT
DESCRIPTION
UNIT
50
Negative MVarhour
MVArh
51
Positive MWatthour
MWh
52
Negative MWatthour
MWh
53
Vg Primary
kV
54
Fault 1 Prefault Phase A Current Magnitude
kA
55
Fault 1 Prefault Phase A Current Angle
degrees
56
Fault 1 Prefault Phase B Current Magnitude
kA
57
Fault 1 Prefault Phase B Current Angle
degrees
58
Fault 1 Prefault Phase C Current Magnitude
kA
59
Fault 1 Prefault Phase C Current Angle
degrees
60
Fault 1 Prefault Phase AB Voltage Magnitude
kV
61
Fault 1 Prefault Phase AB Voltage Angle
degrees
62
Fault 1 Prefault Phase BC Voltage Magnitude
kV
63
Fault 1 Prefault Phase BC Voltage Angle
degrees
64
Fault 1 Prefault Phase CA Voltage Magnitude
kV
65
Fault 1 Prefault Phase CA Voltage Angle
degrees
66
Fault 1 Postfault Phase A Current Magnitude
kA
67
Fault 1 Postfault Phase A Current Angle
degrees
68
Fault 1 Postfault Phase B Current Magnitude
kA
69
Fault 1 Postfault Phase B Current Angle
degrees
70
Fault 1 Postfault Phase C Current Magnitude
kA
71
Fault 1 Postfault Phase C Current Angle
degrees
72
Fault 1 Postfault Phase AB Voltage Magnitude
kV
73
Fault 1 Postfault Phase AB Voltage Angle
degrees
74
Fault 1 Postfault Phase BC Voltage Magnitude
kV
75
Fault 1 Postfault Phase BC Voltage Angle
degrees
76
Fault 1 Postfault Phase CA Voltage Magnitude
kV
77
Fault 1 Postfault Phase CA Voltage Angle
degrees
78
Fault 1 Type
Enum
79
Fault 1 Location
km
ENUM VALUE
FAULT TYPE
0
GROUND
1
PHASE
2
TRIPH
3
AG
4
ABG
5
AB
6
BG
7
BCG
8
BC
9
CG
10
CAG
11
CA
12
NAF
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...