5-108
G650 Generator Protection & Control System
GEK-113285A
5.6 INPUTS/OUTPUTS
5 SETTINGS
5
5.6.4 OUTPUTS
5.6.4.1 OUTPUT SETTINGS DESCRIPTION
Output Logic_0X _0Z:
Type of logic applied to outputs. Possible values are
positive
and
negative
. The default value is
positive. Depending on the type of setting selected, the physical output will be in the same direction (positive) or opposite
(negative) the output activation command.
Output Type_0X _0Z:
Type of output adjusted. Possible values are
normal
,
pulse or latched
, the default value is
Normal
.
Normal
:
The contact output follows the activation command. Remains active while the operation signal is active.
Pulse
:
The contact output remains active the time the operation signal is active plus the pulse output time,
according to the
Pulse Output Time
setting.
Latched
:
The output remains active after the operation signal has been cleared. The reset signal for the latched
outputs is configured at
Setpoint > Relay Configuration > Outputs > Contact Output Reset
”.
Pulse Output Time_0X _0Z:
This is the length of the output pulse in case the output type is selected as
pulse
; the default
value is 10000 ms.
Figure 5–28:shows the types of signals associated to the different output configuration types
.
Figure 5–28: OUTPUT LOGIC TYPES.
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...