GEK-113285A
G650 Generator Protection & Control System
F-5
APPENDIX F
F.1 FACTORY DEFAULT SETTINGS
F
SETPOINT > PRODUCT SETUP > MODBUS USER MAP
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Address 00 for Modbus user map
Address 00
0
N/A
[0000 : FFFF]
Address 01 for Modbus user map
Address 01
0
N/A
[0000 : FFFF]
...
...
...
Address 254 for Modbus user map
Address 254
0
N/A
[0000 : FFFF]
Address 255 for Modbus user map
Address 255
0
N/A
[0000 : FFFF]
SETPOINT > PRODUCT SETUP > FAULT REPORT
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Positive sequence impedance module Pos Seq Module
3.00
0.01 Ohm
[0.01 : 250.00]
Positive sequence impedance angle
Pos Seq Angle
75
1 Deg
[25 : 90]
Zero sequence impedance module
Zero Seq Module
9.00
0.01 Ohm
[0.01 : 750.00]
Zero sequence impedance angle
Zero Seq Angle
75
1 Deg
[25 : 90]
Line length
Line Length
100.0
0.1
[0.0 : 2000.0]
Display fault on HMI
Show Fault On HMI
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PRODUCT SETUP > OSCILLOGRAPHY
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function Permission
Function
ENABLED
N/A
[DISABLED – ENABLED]
Prefault
Trigger Position
30
1%
[5 : 95]
Sampling Rate
Sampling Rate
3600
N/A
[225-450-900-1800-3600]
Maximum number of oscillos
Max. Number Osc.
4
1 oscillo
[1 : 20]
Automatic oscillography overwrite
Automatic Overwrite
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PRODUCT SETUP > DATA LOGGER
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Data logger Rate
Data Logger Rate
1 s
N/A
[1 s, 5 min, 10 min, 15 min,
20 min, 30 min, 60 min.]
Data Logger analog channels X
Data Logger Chnl X
None
N/A
[1 to 16]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...