G650 Generator Protection & Control System
GEK-113285A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
Table 5–58: RESTRICTED GROUND FAULT INTERNAL STATES
5.4.6.1 RESTRICTED GROUND FAULT SETTINGS EXAMPLE
The example does not apply any slope, it is only intended to explain the pickup setting selection when the CT ratios are
different for phases and ground.
•
If the Phase CT Transformers are 400/5 this means a Phase CT Ratio of 80
•
If the Ground CT Transformer is 200/5 this means a Ground CT Ratio of 40
Sensitivity is given in primary amperes with Phase CT Ratio reference, this is:
Sens =[Ground Fault Pickup] x [Phase CT Ratio]
If the Ground Fault Pickup setting is 0.3 A. This setting means that for phases the unit will trip when the Igd with phase
current reference is higher that 24 A, and with ground current reference is higher than 12 A.
RESTRICTED GROUND FAULT INTERNAL STATES
RESTR GND FLT1 PKP
RESTR GND FLT1 OP
RESTR GND FLT2 PKP
RESTR GND FLT2 OP
RESTR GND FLT3 PKP
RESTR GND FLT3 OP
SETPOINT > PROTECTION ELEMENTS > GROUND CURRENT > RESTRICTED GND FAULT >
RESTRICTED GND FAULT 1> RESTRICTED GND FAULT 2 > RESTRICTED GND FAULT 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
Restricted Ground Fault Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Restricted Ground Fault Pickup
Ground Fault Pickup
0.30
0.01 CT
[0.02 : 20.00]
Restricted Ground Fault Slope
Ground Fault Slope
0.00
0.01 %
[0.00 : 100.00]
Restricted Ground Fault Delay
Ground Fault Delay
0.10
0.01 s
[0.00 : 600.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > SYSTEM SETUP > GENERAL SETTINGS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
Phase CT Ratio
Phase CT Ratio
80.0
0.1
[1.0 : 6000.0]
Ground CT ratio
Ground CT Ratio
40.0
0.1
[1.0 : 6000.0]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...