F-6
G650 Generator Protection & Control System
GEK-113285A
F.1 FACTORY DEFAULT SETTINGS
APPENDIX F
F
SETPOINT > PRODUCT SETUP > DEMAND
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Demand Function
DISABLED
N/A
[DISABLED – ENABLED]
Demand method for current values
CRNT Demand
Method
THERMAL
EXPONENTIAL
N/A
[BLOCK INTERVAL -
ROLLING DEMAND -
THERMAL
EXPONENTIAL]
Demand method for Power values
POWER Demand
Method
THERMAL
EXPONENTIAL
N/A
[BLOCK INTERVAL -
ROLLING DEMAND -
THERMAL
EXPONENTIAL]
Demand interval
Demand Interval
5 Minutes
N/A
[5 – 10 – 15 – 20– 30–60]
Trigger Enabled
Trigger Enabled
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > SYSTEM SETUP > GENERAL SETTINGS
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Phase CT ratio
Phase CT Ratio
1.0
0.1
[1.0 : 6000.0]
Ground CT ratio
Ground CT Ratio
1.0
0.1
[1.0 : 6000.0]
Sensitive ground CT ratio
Stv Ground CT Ratio
1.0
0.1
[1.0 : 6000.0]
Phase VT ratio
Phase VT Ratio
1.0
0.1
[1.0 : 6000.0]
Phase VT connection
Phase VT Connection WYE
N/A
[WYE – DELTA]
Rated voltage
Nominal Voltage
100.0
0.1
[1.0 : 500.0]
Rated Frequency
Nominal Frequency
50 Hz
Hz
[50-60]
Phase rotation
Phase Rotation
ABC
N/A
[ABC – ACB]
Frequency reference
Frequency Reference VI
N/A
[VI-VII-VIII]
Auxiliary Voltage
Auxiliary Voltage
VX
N/A
[VX –VN– VG]
Snapshot Event generation
Snapshot Events
DISABLED
N/A
[DISABLED – ENABLED]
Frequency Tracking
Freq. Tracking
DISABLED
N/A
[DISABLED – ENABLED]
SETPOINT > SYSTEM SETUP > FLEX CURVES
FLEX CURVES A > FLEX CURVES B> FLEX CURVES C > FLEX CURVES D
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Values for reset points 0.00 pkp
Time 0.00xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
Values for reset points 0.05 pkp
Time 0.05xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
…
…
…
0.001 s
[0.000 : 65.535]
Values for reset points 0.97 pkp
Time 0.97xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
Values for reset points 0.98 pkp
Time 0.98xPKP [RST] 0.000
0.001 s
[0.000 : 65.535]
Values for operation points 1.03 pkp
Time 1.03xPKP [OP]
0.000
0.001 s
[0.000 : 65.535]
Values for operation points 1.05 pkp
Time 1.05xPKP [OP]
0.000
0.001 s
[0.000 : 65.535]
…
…
…
0.001 s
[0.000 : 65.535]
Values for operation points 19.50 pkp Time 19.50xPKP [OP] 0.000
0.001 s
[0.000 : 65.535]
Values for operation points 20.00 pkp Time 20.00xPKP [OP] 0.000
0.001 s
[0.000 : 65.535]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...