2-16
G650 Generator Protection & Control System
GEK-113285A
2.4 TECHNICAL SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.1.23 OVERFREQUENCY (81O)
2.4.1.24 DIRECTIONAL POWER (32)
Level accuracy
±
0.01 Hz of the reading
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Minimum voltage threshold
30 to 00V in steps of 1 V
Timing accuracy
±3.5% of operate time or 100 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Pickup level
20.00 to 65.00 Hz in steps of 0.01 Hz
Dropout level
Pickup - 0.03 Hz
Level accuracy
±
0.01 Hz of the reading
Trip delay
0.00 to 900.00 s. in steps of 0.01 s
Reset delay
0.00 to 900.00 s. in steps of 0.01 s
Minimum voltage threshold
30 to 00V in steps of 1 V
Timing accuracy
±3.5% of operate time or 100 ms. (whichever is greater)
Snapshot Events
Selectable by setting
Current, Voltage
Fundamental Phasor (primary values)
Number of stages
2
Pickup level (two stages)
-10000.00 to 10000.00 MW (primary values) in steps of
0.01 MW
Characteristic Angle (two stages)
0.00 to 359.99 in steps of 0.01
Accuracy for primary magnitudes
±3% complete range
Trip delay (two stages)
0.00 to 900.00 s in steps of 0.01 s
Timing accuracy
±3.5% of operate time or 50 ms. (whichever is greater)
Block Time after close
0.00 to 900.00 s in steps of 0.01 s
Snapshot Events
Selectable by setting
Operate time:
< 45 ms at 50 Hz, typically
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...