G650 Generator Protection & Control System
A-11
APPENDIX A
A.1 LOGIC OPERANDS
A
Phase IOC High
PH IOC1 HIGH A BLK
Phase instantaneous overcurrent element block Group 1
phase A
PH IOC1 HIGH B BLK
Phase instantaneous overcurrent element block Group 1
phase B
PH IOC1 HIGH C BLK
Phase instantaneous overcurrent element block Group 1
phase C
PH IOC1 HIGH A PKP
Phase instantaneous overcurrent element pickup high
level Group 1 phase A
PH IOC1 HIGH A OP
Phase instantaneous overcurrent element operation
(trip) high level Group 1 phase A
PH IOC1 HIGH B PKP
Phase instantaneous overcurrent element pickup high
level Group 1 phase B
PH IOC1 HIGH B OP
Phase instantaneous overcurrent element operation
(trip) high level Group 1 phase B
PH IOC1 HIGH C PKP
Phase instantaneous overcurrent element pickup high
level Group 1 phase C
PH IOC1 HIGH C OP
Phase instantaneous overcurrent element operation
(trip) high level Group 1 phase C
PH IOC1 HIGH PKP
Phase instantaneous overcurrent element pickup high
level Group 1 any phase
PH IOC1 HIGH OP
Phase instantaneous overcurrent element operation
(trip) high level Group 1 any phase
PH IOC2 HIGH A BLK
Phase instantaneous overcurrent element block Group 2
phase A
PH IOC2 HIGH B BLK
Phase instantaneous overcurrent element block Group 2
phase B
PH IOC2 HIGH C BLK
Phase instantaneous overcurrent element block Group 2
phase C
PH IOC2 HIGH A PKP
Phase instantaneous overcurrent element pickup high
level Group 2 phase A
PH IOC2 HIGH A OP
Phase instantaneous overcurrent element operation
(trip) high level Group 2 phase A
PH IOC2 HIGH B PKP
Phase instantaneous overcurrent element pickup high
level Group 2 phase B
PH IOC2 HIGH B OP
Phase instantaneous overcurrent element operation
(trip) high level Group 2 phase B
PH IOC2 HIGH C PKP
Phase instantaneous overcurrent element pickup high
level Group 2 phase C
PH IOC2 HIGH C OP
Phase instantaneous overcurrent element operation
(trip) high level Group 2 phase C
PH IOC2 HIGH PKP
Phase instantaneous overcurrent element pickup high
level Group 2 any phase
PH IOC2 HIGH OP
Phase instantaneous overcurrent element operation
(trip) high level Group 2 any phase
PH IOC3 HIGH A BLK
Phase instantaneous overcurrent element block Group 3
phase A
PH IOC3 HIGH B BLK
Phase instantaneous overcurrent element block Group 3
phase B
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...