GEK-113285A
G650 Generator Protection & Control System
5-77
5 SETTINGS
5.5 CONTROL ELEMENTS
5
5.5CONTROL ELEMENTS
The G650 incorporates the following control elements:
Setting Group
Underfrequency
Overfrequency
Synchrocheck (25)
Breaker Failure (50BF) (enhanced models only)
VT Fuse Failure (enhanced models only)
Pulse Counters
Analog Comparators
Frequency Rate of Change (81 df/dt)
Phase Shift or Loss of Mains (78V) (enhanced models only)
Loss of Excitation (40)
Accidental Energization (50/27)
Note
: for all control elements related to the breaker, it must be considered that all operations will be performed considering
the status of the switchgear configured as breaker. In
Setpoint > Relay Configuration > Switchgear
up to 16 switchgear
elements can be configured to operate and be monitored, but only one of them can be configured as a breaker, for
monitoring, number of openings and closings counters, (KI)
2
t.
5.5.1 SETTING GROUP
The settings used for setting table management are located in
Setpoint > Control Elements > Setting Group
:
Table 5–77: SETTING GROUP SETTINGS
The snapshot event setting enables or disables the snapshot event generation for this element.
For more detailed information go to section 5.4.1
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP RANGE
Setting Grouping Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Active Group
Active Group
GROUP 1
N/A
[GROUP 1 – GROUP 2 – GROUP 3]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...