GEK-113285A
G650 Generator Protection & Control System
9-7
9 COMMISSIONING
9.7 VERIFICATION OF MEASUREMENT
9
9.7VERIFICATION OF MEASUREMENT
Set the relay as follows
NOTE:
ALL ANGLES INDICATED ARE LAGGING ANGLES
ALL VALUES OBTAINED IN THIS TEST MUST BE THE ONES CORRESPONDING TO THE PHASOR ONES
9.7.1 VOLTAGES
Apply the following voltage and frequency values to the relay:
Verify that the relay measures the values with an error of ±1 % of the applied value plus 0,1% of full scale (275V).
9.7.2 PHASE CURRENTS
Apply the following current and frequency values to the relay:
Verify that the relay measures the values with an error lower than ±0.5% of the test value or ± 10 mA, whichever is greater,
for phases and ground.
Verify that the relay measures the values with an error lower than ±1.5% of the test value or ± 1 mA, whichever is greater,
for sensitive ground (SG).
GENERAL SETTINGS
NAME
VALUE
UNITS
RANGE
PHASE CT RATIO
1.0
0.1
1.0-6000.0
GROUND CT RATIO
1.0
0.1
1.0-6000.0
STV GROUND CT RATIO
1.0
0.1
1.0-6000.0
PHASE VT RATIO
1.0
0.1
1.0-6000.0
PHASE VT CONNECTION
WYE
N/A
WYE – DELTA
NOMINAL VOLTAGE
100 V
0.1
1-250 V
NOMINAL FREQUENCY
50 Hz
1 Hz
50-60 Hz
PHASE ROTATION
ABC
N/A
ABC – ACB
FREQUENCY REFERENCE
VI
N/A
VI-VII-VIII
AUXILIARY VOLTAGE
VX
N/A
VX – VG
FREQ. TRACKING
ENABLED/
DISABLED
N/A
N/A
CHANNEL
ANGLE
FREQUENCY
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
VI
0º
0
5
50
100
150
275
VII
120º
0
5
50
100
150
275
VIII
240º
0
5
50
100
150
275
VX/VG
0º
0
5
50
100
150
275
CHANNEL
ANGLE
FREQUENCY
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
Ia (A)
45º
0
15
10
5
1
0.1
Ib (A)
165º
0
15
10
5
1
0.1
Ic (A)
285º
0
15
10
5
1
0.1
IG (A)
0º
0
15
10
5
1
0.1
ISG (A)
0º
0
5
1
0.1
0.01
0.005
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...