5-66
G650 Generator Protection & Control System
GEK-113285A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
Table 5–66: 59P ELEMENT SETTINGS
Phase overvoltage element settings are:
Function Permission (Function):
This setting indicates whether the phase overvoltage element is enabled or disabled.
Pickup Level:
This is the voltage threshold over which the overvoltage element will operate.
Trip time (Trip Delay):
setting of the Protection element operation time.
Reset time (Reset Delay):
Reset time of the Protection element.
Operation logic (Logic):
This setting allows the element operation logic selection:
ANY PHASE
The element will operate under an overvoltage condition in any of the
three phases.
TWO PHASES The element will operate under an overvoltage condition in at least
two phases.
ALL PHASES
The element will operate under an overvoltage condition in the three
phases.
Snapshot Events:
The snapshot event setting enables or disables the snapshot event generation for this
element.
5.4.9.3 NEUTRAL OVERVOLTAGE ELEMENT (HIGH LEVEL) (59NH)
The Neutral Overvoltage element can be used to detect an asymmetrical system voltage condition due to a ground fault or
to the loss of one or two phases of the source.
The element responds to the system neutral voltage (3V0), calculated from the phase voltages (if V
X
or V
G
is selected as
as Auxiliary Voltage in General Settings) or measured by the 4th voltage transformer (if V
N
is selected as Auxiliary voltage
in General Settings).
VT errors and normal voltage unbalance must be considered when setting this element.
The element time delay is selectable between 0 and 900 seconds and incorporates a reset with a selectable delay between
0 and 900 seconds.
Notice that the neutral overvoltage element will not be available if a
DELTA
Connection is set in the
Phase VT Connection
setting in General settings (the Auxiliary Voltage setting is set to VX or VG). This is because with this combination of
settings it is not possible to calculate the zero sequence component from the phase-to-phase voltage magnitudes.
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS > PHASE OV >
PHASE OV 1> PHASE OV 2 > PHASE OV 3
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup Level
Pickup Level
10
1 V
[3 : 500]
Trip time
Trip Delay
10.00
0.01 s [0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s [0.00 : 900.00]
Operation logic
Logic
ANY PHASE
N/A
[ANY PHASE – TWO PHASES – ALL PHASES]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...