GEK-113285A
G650 Generator Protection & Control System
5-39
5 SETTINGS
5.4 PROTECTION ELEMENTS
5
5.4.2.8 USER CURVES - FLEXCURVES A/B/C/D
The relay incorporates 4 user curves called User Curve A, B, C and D. The points for these curves are defined by the user.
Each of the four curves has an operation characteristic (operate), defined by 80 points, and a reset characteristic, defined
by 40 points. Each point is defined as a time value for each I/I
pickup
value (number of times the pickup current) given on the
table. The user can assign values between 0 and 65.535 seconds in steps of 1 ms.
The following table details the 120 points as well as the characteristic for each of them, and a blank cell where the user can
write the time value when the operation (for I > I
pickup
) or the reset (for I < I
pickup
) is required,
Table 5–38: USER CURVE CHARACTERISTICS
The two first columns (40 points) correspond to the RESET curve. The other 4 columns, with 80 points in total, correspond
to the OPERATE curve. The reset characteristic values are between 0 and 0.98, and the operation values are between
1.03 and 20.
The final curve will be created by means of a linear interpolation from the points defined by the user. This is a separate
process for the RESET and the OPERATE curve.
The definition of these points is performed in a separate module from the relay, using a configuration program included in
the EnerVista 650 Setup, which incorporates a graphical environment for viewing the curve, thus making it easy for the user
to create it. This module can be accessed from the “Edit Curve” option in the FlexCurve menu, at
Setpoint > System
Setup > Flex Curves
.
RESET
(XPKP)
TIME
(S)
RESET
(XPKP)
TIME
(S)
OPERATE
(XPKP)
TIME
(S)
OPERATE
(XPKP)
TIME
(S)
OPERATE
(XPKP)
TIME
(S)
OPERATE
(XPKP)
TIME
(S)
0.00
0.68
1.03
2.9
4.9
10.5
0.05
0.70
1.05
3.0
5.0
11.0
0.10
0.72
1.1
3.1
5.1
11.5
0.15
0.74
1.2
3.2
5.2
12.0
0.20
0.76
1.3
3.3
5.3
12.5
0.25
0.78
1.4
3.4
5.4
13.0
0.30
0.80
1.5
3.5
5.5
13.5
0.35
0.82
1.6
3.6
5.6
14.0
0.40
0.84
1.7
3.7
5.7
14.5
0.45
0.86
1.8
3.8
5.8
15.0
0.48
0.88
1.9
3.9
5.9
15.5
0.50
0.90
2.0
4.0
6.0
16.0
0.52
0.91
2.1
4.1
6.5
16.5
0.54
0.92
2.2
4.2
7.0
17.0
0.56
0.93
2.3
4.3
7.5
17.5
0.58
0.94
2.4
4.4
8.0
18.0
0.60
0.95
2.5
4.5
8.5
18.5
0.62
0.96
2.6
4.6
9.0
19.0
0.64
0.97
2.7
4.7
9.5
19.5
0.66
0.98
2.8
4.8
10.0
20.0
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...