GEK-113285A
G650 Generator Protection & Control System
2-29
2 PRODUCT DESCRIPTION
2.4 TECHNICAL SPECIFICATIONS
2
2.4.9 CONTROL POWER SUPPLY
2.4.10 COMMUNICATIONS
LOW RANGE (LO)
Nominal DC Voltage:
24 to 48 V
Min/Max DC Voltage
19.2 / 57.6 V
Note:
Low range is DC only
HIGH RANGE (HI)
Nominal DC Voltage:
110 to 250 V
Min/Max DC Voltage
88 / 300 V
Nominal AC Voltage:
120 to 230 V
Min/Max AC Voltage
102 / 250 V
ALL RANGES
Voltage Loss hold-up time
200 ms typical, worst case 100 ms without unit reset
Power consumption
Typical =25 VA, Maximum =45 VA
Display backlight auto power-off mode after 15 minutes without touching any key, in order to ensure long life and minimum
consumption.
FRONT PORT:
Front port:
COM2
Type
RS232
Baud Rate
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 y 115200 bauds
Default Baud Rate
19200
Protocols available:
ModBus
®
RTU / DNP 3.0
Typical distance:
1200 m
Isolation:
2 kV
ASYNCHRONOUS REAR PORTS:
None or two rear ports (depending on
model):
COM1, COM2 (rear COM2 multiplexed with front port)
Type (depending on model):
Model F
None
Model A
Redundant RS485
Model X
Redundant RS485 + fiber CAN for inputs/outputs module
Model P
Redundant 1mm-plastic F.O.
Model Y
Redundant 1mm-plastic F.O. + fiber CAN for inputs/outputs module
Model G
Redundant multimode glass F.O.
Model Z
Redundant multimode glass F.O. + fiber CAN for inputs/outputs module
Model C
Cable CAN port for I/O module
Model M
Cable CAN port for I/O module (cable) + RS485 (ModBus RTU)
Optic Features for ST connectors
devices:
Wave length: 1300nm
Fiber type: multimode 62.5/125
μ
m or 50/125
μ
m
Baud Rate:
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 y 115200 bauds
Default Baud Rate
19200
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...