11 FREQUENTLY ASKED QUESTIONS
11.2 PROTECTION
11
11.2PROTECTION
Q1.
Does the G650 support IRIG-B signals? Which type and accuracy? How many units may be connected to the
same source?
A1.
Yes, the G650 includes an IRIG-B input for all models, including the basic ones.
It uses DC level format B. Formats used are B0000, B0002 and B0003.
Actual accuracy is 1 millisecond. Internal sampling rate allows true 1 ms accuracy time tagging.
The input burden is very low. The maximum number of units that may be connected to a generator depends on its
output driving capability. Up to 60 units have been successfully connected with equipments commonly used in the
market.
Q2.
Does the equipment work with dry inputs in both AC and DC?
A2.
The equipment works only with DC inputs.
Inputs should be driven with externally generated DC current. No special 48 Vdc or other outputs are included in the
equipment to drive these inputs; therefore, contacts connected to the equipment should be connected to a DC
source.
Q3.
Is it oscillography programmable?
A3.
Yes, the sampling rate is programmable (4, 8, 16, 32 or 64 samples per input). The depth will depend on the
sampling rate.
Q4.
Do I have to select a different model for 1 or 5 A?
A4.
No. The same model is able to work with either /1 A or /5 A rated secondary currents. There are high accuracy
sensing transformers that allow the use of any current input through the same terminals to reduce the spares and
simplify wiring.
Q5.
In my installation, several digital inputs become active when I energize the transformer. How can I reduce
sensitivity?
A5.
By selecting debounce time and/or voltage threshold, the relay may adapt its sensitivity to different applications.
Please select the maximum voltage threshold and debounce time (recommended 15 ms) to minimize AC coupling
effects.
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...