G650 Generator Protection & Control System
GEK-113285A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
Table 5–63: GENERATOR UNBALANCE ELEMENT SETTINGS
•
Gen Unbal Function
: This setting allows enabling or disabling the element.
•
Gen Unbal Inom
: This setting is the rated full load current of the machine.
•
Gen Unbal Stg1 Pkp
: This setting defines the pickup of the stage 1 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting. It is typically set at the maximum continuous negative
sequence current rating of the machine.
•
Gen Unbal Stg1 K
: This setting is the negative sequence capability constant. This value is normally provided by the
generator manufacturer.
•
Gen Unbal Stg1 Tmin
: This is the minimum operate time of the element.
•
Gen Unbal Stg1 Tmax
: This is the maximum operate time of the element. This setting can be applied to limit the
maximum tripping time.
•
Gen Unbal Stg1 K-Rst
: This setting defines the linear reset rate of the stage. This feature provides a thermal memory
of previous unbalance conditions.
•
Gen Unbal Stg2 Pkp
: This setting defines the pickup of the stage 2 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting.
•
Gen Unbal Stg2 Delay
: This is the minimum operate time of the stage 2 element.
Table 5–64: GENERATOR UNBALANCE INTERNAL SIGNALS
SETPOINT > PROTECTION ELEMENTS > NEGATIVE SEQUENCE CURRENT > GENERATOR UNBALANCE >
GENERATOR UNBALANCE 1> GENERATOR UNBALANCE 2 > GENERATOR UNBALANCE 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
Function Permision
Function
DISABLED
N/A
[DISABLED – ENABLED]
Generator Rated Full Load Current
Gen Unbal Inom
5.00
0.01 A
[0.00 : 10.00]
Pickup level for stage 1 (as a percentage of
Gen Unbal Inom)
Gen Unbal Stg1 Pkp
8.00
0.01 %
[0.00 : 100.00]
K (Negative sequence capability constant) for
stage 1
Gen Unbal Stg1 K
1.00
0.01
[0.00 : 100.00]
Minimum Operating time for stage 1
Gen Unbal Stg1 Tmin
0.3
0.1 s
[0.0 : 1000.0]
Maximum Operating time for stage 1
Gen Unbal Stg1 Tmax
600.0
0.1 s
[0.0 : 1000.0]
K for Linear reset of the stage
Gen Unbal Stg1 K-Rst
240.0
0.1
[0.0 : 1000.0]
Pickup level for stage 2 (as a percentage of
Gen Unbal Inom)
Gen Unbal Stg2 Pkp
3.00
0.01 %
[0.00 : 100.00]
Trip time for stage 2
Gen Unbal Stg2 Delay
5.0
0.1s
[0.0 : 1000.0]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SIGNAL
COMMENT
GEN UNBAL (1, 2, 3) BLOCK
Input used to block the element (1, 2, 3) externally
GEN UNBAL (1, 2, 3) STG1 PKP Output used to indicate I2/Inom ratio above stage 1 setting
in units (1, 2, 3)
GEN UNBAL (1, 2, 3) STG1 OP
Output used to indicate stage 1 operation in units (1, 2, 3)
GEN UNBAL (1, 2, 3) STG2 PKP Output used to indicate I2/Inom ratio above stage 2 setting
in units (1, 2, 3)
GEN UNBAL (1, 2, 3) STG2 OP
Output used to indicate stage 2 operation in units (1, 2, 3)
GEN UNBAL1 PKP
This status is a logic OR between the GEN UNBAL(1, 2, 3)
STG1 PKP and GEN UNBAL(1, 2, 3) STG2 PKP
GEN UNBAL1 OP
This status is a logic OR between the GEN UNBAL(1, 2, 3)
STG1 OP and GEN UNBAL(1, 2, 3) STG2 OP
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...