GEK-113285A
G650 Generator Protection & Control System
5-97
5 SETTINGS
5.5 CONTROL ELEMENTS
5
5.5.10
LOSS OF MAINS (78V) (FOR ENHANCED MODELS)
5.5.10.1 INTRODUCTION
The Phase Shift or Loss of main element (78V) measures the length of each cycle of the voltage signal. When a generator
becomes disconnected, the sudden change in load causes a sudden change in cycle length. The single cycle becomes
shifted with time.Therefore the 78V element can be used to detect disconnection from the grid.
A phase displacement is defined as a sudden change in the voltage, which can be generated by a big load increase or a
sudden loss load. The loss of mains element detects a phase displacements comparing the period of the last cycle length
with the period average of last N cycles. If the difference between these two values is above setting the element picks up
and operates.
Figure 5–22: VOLTAGE PHASE DISPLACEMENT EXAMPLE
5.5.10.2 LOSS OF MAINS SETTINGS DESCRIPTION
The settings can be selected at
Setpoint > Control Elements > Loss of Mains
Table 5–94: LOSS OF MAINS ELEMENT SETTINGS
•
Function
: This setting allows enabling or disabling the Loss of Mains element.
•
Loss of mains Mode
: ONE PHASE option: the loss of mains element gives indication when a phase displacement
occurs in any phase..
•
Phase Shift Angle
: This setting defines the minimum detected angle difference to operate the element.
•
Minimum Voltage
: If measured voltage is below this setting, the unit will be blocked
•
Snapshot Events
: The snapshot event setting enables or disables the snapshot event generation for this element.
SETPOINT > CONTROL ELEMENTS > LOSS OF MAINS >
LOSS OF MAINS 1> LOSS OF MAINS 2 > LOSS OF MAINS 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
Function Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Any phase displacement mode to operate
Loss of Mains Mode
ONE PHASE
N/A
[ONE PHASE]
Minimum Phase shift angle value to operate
Phase Shift Angle
1.00
0.01 Deg [2.00 : 22.00]
Minimum voltage threshold
Minimum Voltage
70
1 V
[30 : 500]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
-150
-100
-50
0
50
100
150
0
50
100
150
200
250
Voltage w ith no fault
Voltage w ith phase displacement
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...