A-26
G650 Generator Protection & Control System
GEK-113285A
A.1 LOGIC OPERANDS
APPENDIX A
A
OPERANDS - G650 - MODEL FX - GX
INTERNAL SYSTEM STATUS (CONT.)
Breaker Status
BREAKER OPEN
Breaker Opened
BREAKER CLOSED
Breaker closed
BREAKER UNDEFINED Breaker undefined (52a and 52b have the same status)
Breaker Failure(Enhanced models only)
BKR FAIL INITIATE
Breaker failure initiation
BKR FAIL NO
CURRENT
Breaker failure without current
BKR FAIL
SUPERVISION
Breaker failure 1st level (supervision – retrip)
BKR FAIL HISET
Breaker failure 2nd level (high level)
BKR FAIL LOWSET
Breaker failure 3rd level (low level)
INTERNAL ARC
Internal arc
BKR FAIL 2nd STEP
Breaker failure second step
Synchrocheck
Synchrocheck BLK INP
Synchronism element block
Synchrocheck OP
Synchronsim condition (Dv, Dj and Df are within the set
range)
SYNCHK CLOSE PERM Closing permission for the synchronism element:
(SYNCHK OP) OR (SYNCHK CON OP)
Synchrocheck COND
OP
Active if when it is set, any of the three following
conditions is met:
DL-DB OPERATION
Dead line – dead bus condition
DL-LB OPERATION
Dead line – live bus condition
LL-DB OPERATION
Live line – dead bus condition
SLIP CONDITION
Slip conditions are met
BUS FREQ > LINE
FREQ
Bus Frequency higher than line frequency
BUS FREQ < LINE
FREQ
Bus Frequency lower than line frequency
Default Channel (not used)
Default Channel
Channel not used
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...