6-30
G650 Generator Protection & Control System
GEK-113285A
6.2 STATUS
6 ACTUAL VALUES
6
6.2.12.7 BREAKER MAINTENANCE
Actual> Status > Records Status > Breaker Maintenance
This screen shows the breaker status related to breaker maintenance. Other statuses are provided in the different
switchgear or breaker status signals.
Table 6–34: BREAKER MAINTENANCE STATUS
The breaker maintenance inputs are signals that can be configured at Setpoint > Relay Configuration > Protection
Elements:
RESET KI2t COUNTERS
Signal to reset and set to zero all the KI2t counters (for all phases)
RESET BKR COUNTERS
Signal to reset and set to zero all the breaker counters (number of openings and closings
and alarms)
KI2t PHASE A ALARM
Alarm signal for maximum breaking capacity in phase A exceeded
KI2t PHASE B ALARM
Alarm signal for maximum breaking capacity in phase B exceeded
KI2t PHASE C ALARM
Alarm signal for maximum breaking capacity in phase C exceeded
BKR OPENINGS ALARM
Alarm related to the maximum number of breaker openings
BKR OPEN 1 HOUR ALARM Alarm related to the maximum number of breaker openings in one hour
BREAKER OPENINGS
Counter of the total number of openings performed by the breaker
BREAKER CLOSINGS
Counter of the total number of closings performed by the breaker
KI2t PHASE A
kI
2
t phase A counter (total accumulative breaking level – phase A)
KI2t PHASE B
kI
2
t phase B counter (total accumulative breaking level – phase B)
KI2t PHASE C
kI
2
t phase C counter (total accumulative breaking level – phase C)
BKR OPENING TIME
Time to set a failure in opening the breaker.
BKR CLOSING TIME
Time to set a failure in closing the breaker.
Breaker opening and closing time signals are configured at
Setpoint > Relay Configuration > Switchgear
for the related
switchgear device.
BREAKER MAINTENANCE INPUTS
RESET KI2t COUNTERS
RESET BKR COUNTERS
BREAKER MAINTENANCE STATUS
KI2t PHASE A ALARM
KI2t PHASE B ALARM
KI2t PHASE C ALARM
BKR OPENINGS ALARM
BKR OPEN 1 HOUR ALARM
BREAKER OPENINGS
BREAKER CLOSINGS
KI2t PHASE A
KI2t PHASE B
KI2t PHASE C
BKR OPENING TIME
BKR CLOSING TIME
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...