R43698F
G2_1PDELAY1
1PDELAY1
0.1 to 300.0 sec. step 0.1
R/W
Float
R43700F
G2_1PDELAY2
1PDELAY2
0.1 to 300.0 sec. step 0.1
R/W
Float
R43702F
G2_1PDELAY3
1PDELAY3
0.1 to 300.0 sec. step 0.1
R/W
Float
R43704F
G2_1PDELAY4
1PDELAY4
0.1 to 300.0 sec. step 0.1
R/W
Float
R43706I
G2_NUM_3P_AT
NUM_3P_AT
1, 2, 3, 4
R/W
INT
R43707F
G2_3PDELAY1
3PDELAY1
0.1 to 300.0 sec. step 0.1
R/W
Float
R43709F
G2_3PDELAY2
3PDELAY2
0.1 to 300.0 sec. step 0.1
R/W
Float
R43711F
G2_3PDELAY3
3PDELAY3
0.1 to 300.0 sec. step 0.1
R/W
Float
R43713F
G2_3PDELAY4
3PDELAY4
0.1 to 300.0 sec. step 0.1
R/W
Float
R43715F
G2_RESETTIME
RESETTIME
0.1 to 300.0 sec. step 0.1
R/W
Float
R43717F
G2_DWELLTIME
DWELLTIME
0.1 to 2.0 sec. step 0.1
R/W
Float
R43719I
G2_HOLD
HOLD
0 = No; 1 = Yes
R/W
INT
R43720I
G2_HOLDTIME
HOLDTIME
1 to 1000 sec. step 1
R/W
INT
R43721I
G2_HOLDSENSE
HOLDSENSE
0 = CC; 1 = CO
R/W
INT
R43722I
G2_SYNCHCHECK
SYNCHCHECK
0 = No, 1 = Yes
R/W
INT
R43723F
G2_CLOSEANG
CLOSEANG
0 to 75° step 1
R/W
INT
R43725F
G2_SLIPFREQ
SLIPFREQ
0.1 to 5.0 Hz step 0.1
R/W
Float
R43727I
G2_BUSLINE
BUSLINE
0 = BUS; 1 = LINE
R/W
INT
R43728I
G2_SYNCHPHASE
SYNCHPHASE
0 = VA; 1 = VB; 2 = VC
3 = VAB; 4 = VBC; 5 = VCA
R/W
INT
R43729I
G2_SYNCHHOLD
SYNCHHOLD
1 to 100 sec. step 1
R/W
INT
R43730I
G2_SP1DELAY2
SP1DELAY2
0 = No; 1 = Yes
R/W
INT
R43731I
G2_SP1DELAY3
SP1DELAY3
0 = No; 1 = Yes
R/W
INT
R43732I
G2_SP1DELAY4
SP1DELAYR
0 = No; 1 = Yes
R/W
INT
R43733I
G2_SP3DELAY1
SP3DELAY1
0 = No; 1 = Yes
R/W
INT
R43734I
G2_SP3DELAY2
SP3DELAY2
0 = No; 1 = Yes
R/W
INT
R43735I
G2_SP3DELAY3
SP3DELAY3
0 = No; 1 = Yes
R/W
INT
R43736I
G2_SP3DELAY4
SP3DELAY4
0 = No; 1 = Yes
R/W
INT
R43737I
G2_SYNCMANCLS
SYNCMANCLS
0 = No; 1 = Yes
R/W
INT
R43738F
G2_VBUSLIVE
VBUSLIVE
0.1 to 130 V step 0.1
R/W
Float
R43740F
G2_VBUSDEAD
VBUSDEAD
0.1 to 130 V step 0.1
R/W
Float
R43742F
G2_VLINELIVE
VLINELIVE
0.1 to 130 V step 0.1
R/W
Float
R43744F
G2_VLINEDEAD
VLINEDEAD
0.1 to 130 V step 0.1
R/W
Float
R43746I
G2_LBUSDLINE
LBUSDLINE
0 = No; 1 = Yes
R/W
INT
R43747I
G2_DBUSLLINE
DBUSLLINE
0 = No; 1 = Yes
R/W
INT
R43748I
G2_DBUSDLINE
DBUSDLINE
0 = No; 1 = Yes
R/W
INT
R43749F
G2_DELTAV
DELTAV
0.1 to 130 V step 0.1
R/W
Float
R43751I
G2_DELTAVBLK
DELTAVBLK
0 = No; 1 = Yes
R/W
INT
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 13 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...