2-
64
LPS-D Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
614
51GCURVE
51G Curve
INV, V-INV, E-INV, CUSTOM, DEFT
V-INV
615
51GTIMDIAL
51G Time Dial
0.5 to 10.0 step 0.1
5
616
DEFTIMDELY
Definite Time Delay
0.5 to 30.0 sec. step 0.1
1.0 sec.
617
51G_RESET
51G Reset Characteristic
FAST, EM
FAST
VOLTAGE
701
RATEDVOLTS
Rated Per Unit Voltage
100, 105,110,115, 120 volts
115 volts
702
PHASEOVER
Select Phase Overvoltage
NO, YES
NO
703
PHOVPICKUP
Phase Overvoltage Pickup
0.0 to 1.4 p.u. volts step 0.01
1.4 V
704
PHOVTMDLY
Phase Overvoltage Time Delay
0.0 to 10.0 sec. step 0.01
0.50 sec.
705 to 713 Not used
714
FUSEFAIL
Potential Fuse Failure Blocking
NO, YES
YES
BLK RECLOS
801
ALL_BELOW
Block reclosing for any function
NO, YES
NO
802
OUTOFSTEP
Block for Out of Step
NO, YES
NO
803
ALL_3_Z2PH
Block for 3 phase faults
NO, YES
NO
804
50G_BLOCK
Block for 50G trip
NO, YES
NO
805
Z2TIMETRIP
Block for Z2 Time Delayed Trip
NO, YES
NO
806
Z3TIMETRIP
Block for Z3 Time Delayed Trip
NO, YES
NO
807
Z4TIMETRIP
Block for Z4 Time Delayed Trip
NO, YES
NO
808
Z1PHASTRIP
Block for any Z1 Phase Fault
NO, YES
NO
809
ANYZ2PHASE
Block for any Z2 Phase Fault
NO, YES
NO
810
CONFGTRIP
Block For Configurable Trip
Logic
NO, YES
NO
LINEPICKUP
901
LINEPICKUP
Select Line Pickup
NO, YES
NO
902
BYPASSTL3
Bypass Line Pickup Time Delay
NO, YES
NO
903
I1PICKUP
I1 Pickup
1.0 to 15.0 amps
step 0.1
0.2 to 3.0 amps
step 0.1
3.0 A at 5A
0.6 A at 1A
REMOTEOPEN (THREE PHASE SYSTEMS ONLY)
1001
R E M O TE O P E N
Select Remote Open Detector
NO, YES
NO
Table 2–8: PROTECTION SETTINGS GUIDE (Sheet 4 of 9)
No.
M nem onic
Description
Range (5A)
Range (1A)
Default
†
Setting/value is applicable to LPS-D Revision B models only.
‡
Setting/value is applicable LPS-D Single Phase Tripping models only.
^
Setting/value is applicable to LPS-D Three Phase Tripping models only.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...