LPS-D Line Protection System
2-
67
2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
2
1806
1PDELAY3
1 Pole Third Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1807
1PDELAY4
1 Pole Fourth Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1808
NUM3P
Number of Attempts Following
3P Trip
1 to 4 step 1
1
1809
3PDELAY1
3 Pole First Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1810
3PDELAY2
3 Pole Second Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1811
3PDELAY3
3 Pole Third Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1812
3PDELAY4
3 Pole Fourth Delay
0.1 to 300 sec. step 0.1
0.1 sec.
1813
RESETTIME
Reset Time
0.1 to 300 sec. step 0.1
1 sec.
1814
DWELLTIME
Contact Dwell Time
0.1 to 2 sec. step 0.1
0.1 sec.
1815
HOLD
Inhibit Hold Select
YES, NO
NO
1816
HOLDTIME
Inhibit Hold Time
1 to 1000 sec. step 1
1 sec.
1817
HOLDSENSE
Contact Input Status
CC, CO
CC
1818
SYNCCHECK
Synch Check Supervision
YES, NO
NO
1819
CLOSEANG
Closing Angle
0 to 75° step 1
30°
1820
SLIPFREQ
Slip Frequency
0.1 to 5 Hz step 0.1
1 Hz
1821
BUSLINE
Bus or Line Voltage
BUS, LINE
LINE
1822
SYNCPHASE
Voltage used by SYNCCHECK
VA, VB, VC, VAB, VBC, VCA
VA
1823
SYNCHOLD
SYNCCHECK Hold Time
1 to 100 sec. step 1
1 sec.
1824
SP1DELAY2
Supervise 2nd 3P Reclose after
1P Trip
YES, NO
NO
1825
SP1DELAY3
Supervise 3rd 3P Reclose after
1P Trip
YES, NO
NO
1826
SP1DELAY4
Supervise 4th 3P Reclose after
1P Trip
YES, NO
NO
1827
SP3DELAY1
Supervise 1st 3P Reclose after
3P Trip
YES, NO
NO
1828
SP3DELAY2
Supervise 2nd 3P Reclose after
3P Trip
YES, NO
NO
1829
SP3DELAY3
Supervise 3rd 3P Reclose after
3P Trip
YES, NO
NO
1830
SP3DELAY4
Supervise 4th 3P Reclose after
3P Trip
YES, NO
NO
Table 2–8: PROTECTION SETTINGS GUIDE (Sheet 7 of 9)
No.
M nem onic
Description
Range (5A)
Range (1A)
Default
†
Setting/value is applicable to LPS-D Revision B models only.
‡
Setting/value is applicable LPS-D Single Phase Tripping models only.
^
Setting/value is applicable to LPS-D Three Phase Tripping models only.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...