GE Power Management
LPS-D Line Protection System
B-
15
APPENDIX B
B.1 MEMORY MAPPING
B
R43620I
G2_ALL_3_Z2PH
ALL_3_Z2PH
0 = No; 1 = Yes
R/W
INT
R43621I
G2_50G_BLOCK
50G_BLOCK
0 = No; 1 = Yes
R/W
INT
R43622I
G2_Z2TIMETRIP
Z2TIMETRIP
0 = No; 1 = Yes
R/W
INT
R43623I
G2_Z3TIMETRIP
Z3TIMETRIP
0 = No; 1 = Yes
R/W
INT
R43624I
G2_Z4TIMETRIP
Z4TIMETRIP
0 = No; 1 = Yes
R/W
INT
R43625I
G2_Z1PHASTRIP
Z1PHASTRIP
0 = No; 1 = Yes
R/W
INT
R43626I
G2_ANYZ2PHASE
ANYZ2PHASE
0 = No; 1 = Yes
R/W
INT
R43627I
G2_CONFGTRIP
CONFGTRIP
0 = No; 1 = Yes
R/W
INT
R43628I
G2_LINEPICKUP
LINEPICKUP
0 = No; 1 = Yes
R/W
INT
R43629I
G2_BYPASSTL3
BYPASSTL3
0 = No; 1 = Yes
R/W
INT
R43630F
G2_I1PICKPU
I1PICKUP
1.0 to 15.0 A step 0.1
0.2 to 3.0 A step 0.1
R/W
Float
R43632I
G2_REMOTEOPEN
REMOTEOPEN
0 = No; 1 = Yes
R/W
INT
R43633I
G2_TL20PICKUP
TL20PICKUP
10 to 100 msec. step 1
R/W
INT
R43634I
G2_LINEOVERLD
LINEOVERLD
0 = No; 1 = Yes
R/W
INT
R43635F
G2_LEVEL1PU
LEVEL1PU
2.5 to 20.0 A step 0.1 (5A)
0.5 to 4.0 A step 0.1 (1A)
R/W
Float
R43637F
G2_LEVEL2PU
LEVEL2PU
5.0 to 40.0 A step 0.1 (5A)
1.0 to 8.0 A step 0.1 (1A)
R/W
Float
R43639F
G2_LEVEL1TDLY
LEVEL1TDLY
10 to 200 sec. step 1
R/W
Float
R43641F
G2_LEVEL2TDLY
LEVEL2TDLY
10 to 99 sec. step 1
R/W
Float
R43643I
G2_PICKSCHEME
PICKSCHEME
0 = STEPDST; 1 = PUTT;
2 = POTT1; 3 = POTT2;
4 = HYBRID
R/W
INT
R43644I
G2_NUMRCVR
NUMRCVR
0, 1, 2
R/W
INT
R43645I
G2_TRIPMODE
TRIPMODE
0 = 3POLE; 1 = 1POLE;
2 = 1POLEZ2
R/W
INT
R43646I
G2_CARRSTART
CARRSTART
0 = DIR; 1 = IPB; 2 = FD
R/W
INT
R43647I
G2_WKINFTRIP
WKINFTRIP
0 = No; 1= Yes
R/W
INT
R43648I
G2_TL1PICKUP
TL1PICKUP
1 to 200 msec. step 1
R/W
INT
R43649I
G2_TL4PICKUP
TL4PICKUP
0 to 50 msec. step 1
R/W
INT
R43650I
G2_TL4DROPOUT
TL4DROPOUT
0 to 50 msec. step 1
R/W
INT
R43651I
G2_TL5PICKUP
TL5PICKUP
0 to 200 msec. step 1
R/W
INT
R43652I
G2_TL5DROPOUT
TL5DROPOUT
0 to 200 msec. step 1
R/W
INT
R43653I
G2_TL6PICKUP
TL6PICKUP
0 to 200 msec. step 1
R/W
INT
R43654I
G2_TL6DROPOUT
TL6DROPOUT
0 to 200 msec. step 1
R/W
INT
R43655I
G2_TL16PICKUP
TL16PICKUP
8 to 99 msec. step 1
R/W
INT
R43656I
G2_TL24DROPOUT
TL24DROPOUT
30 to 500 msec. step 1
R/W
INT
R43657I
G2_TL25DROPOUT
TL25DROPOUT
30 to 500 msec. step 1
R/W
INT
R43658I
G2_TL26PICKUP
TL26PICKUP
0 to 50 msec. step 1
R/W
INT
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 11 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...