2-
74
LPS-D Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
211
‡
Z2RGREACH
Zone 2 Resistive Ground
Reach
0.01 to 100.00
Ω
step 0.01
0.05 to 500
Ω
step 0.01
Z3DISTANCE
301
Z3PHASE
Z3 Phase Distance
NO, YES
302
Z3PHREACH
Z3 Phase Reach
0.01 to 50.0
Ω
step 0.01
0.05 to 250.0
Ω
step 0.05
303
Z3PCHARANG
Z3 Phase Characteristic Angle
90° to 120° step 5
304
Z3GROUND
Z3 Ground Distance
NO, YES
305
Z3GRDREACH
Z3 Ground Reach
0.01 to 50.0
Ω
step 0.01
0.05 to 250.0
Ω
step 0.05
306
Z3G C H A R A N G
Z3 Ground Characteristic Angle
80° to 155° step 5
307
Z3P_TIME
Z3 Phase Timer
0.10 to 10.0 sec. step 0.01
308
Z3G_TIME
Z3 Ground Timer
0.10 to 10.0 sec. step 0.01
309
‡
Z3GRDCHAR
Z3 Ground Characteristic
MHO, QUAD
†
310
‡
Z3RGREACH
Z3 Resistive Ground Reach
0.01 to 100.00
Ω
step 0.01
0.05 to 500
Ω
step 0.01
Z4DISTANCE
401
Z4PHASE
Z4 Phase Distance
NO, YES
402
Z4PHREACH
Z4 Phase Reach
0.01 to 50.0
Ω
step 0.01
0.05 to 250.0
Ω
step 0.05
403
Z4PCHARANG
Z4 Phase Characteristic Angle
80° to 120° step 5
404
Not Used
405
Z4GRND
Z4 Ground Distance
NO, YES
406
Z4G R D R E A C H
Z4 Ground Reach
0.01 to 50.0
Ω
step 0.01
0.01 to 250.0
Ω
step 0.05
407
Z4G C H A R A N G
Z4 Ground Characteristic Angle
80° to 155° step 5
408
Z4DIRECTN
Z4 Direction
FORWRD, REVERS
409
Z4_TIMERS
Z4 Timers
NO, YES
410
Z4P_TIME
Z4 Phase Timer
0.10 to 10.0 sec. step 0.01
411
Z4G_TIME
Z4 Ground Timer
0.10 to 10.0 sec. step 0.01
412
‡
Z4GRDCHAR
Z4 Ground Characteristic
MHO, QUAD
†
413
‡
Z4RGREACH
Z4 Resistive Ground Reach
0.01 to 100.00
Ω
step 0.01
0.05 to 500
Ω
step 0.01
Table 2–10: PROTECTION SETTINGS DATA SHEET (Sheet 2 of 9)
No.
M nem onic
Description
Range (5A)
Range (1A)
User Setting
†
Setting value QUAD applies to LPS-D Revision B models only.
‡
Setting is applicable to Revision B models only.
^
Setting is applicable to LPS-D models with three phase tripping only.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...