1 PRODUCT DESCRIPTION
1.7 SELF-TEST FEATURES
1
The components tested in the background are listed in Table 9–2: RUN-TIME BACKGROUND SELF-TESTS
on page 9–2. Testing of I/O hardware is done in the foreground, so that the processors know when a given
component or port is in use and therefore not available for testing. The components tested in the foreground
are listed in Table 9–3: RUN-TIME FOREGROUND SELF-TESTS on page 9–2. Some foreground tests are
performed every sample period, while others are performed less frequently.
As with background self-tests, any failed foreground test is repeated and must fail three consecutive times to
be considered a failure. Although not specifically a self-test, the trip circuit continuity monitoring is performed
as a foreground test. Refer to Section 1.5.13: TRIP CIRCUIT MONITOR on page 1–21.
The operator may initiate a visual-response test of the keypad and LCD display components. Refer to Chapter
4: ACCEPTANCE/PERIODIC TESTS for details.
1.7.3 CONTINUOUS MONITOR
The LPS-D relay includes a continuous monitor feature in addition to its self-test features. The continuous
monitor is intended to detect any LPS-D tripping units (Zone 2 or Zone 3 distance functions, 50G or 50 overcur-
rent functions) that are in the picked-up condition without a corresponding operation of the Fault Detector. If
such a condition occurs and persists for 1 second, the LPS-D relay will issue a non-critical alarm and log a con-
tinuous monitor event.
These continuous monitor alarm points can be found in Table 2–7: INDEX NUMBERS – scheme, recloser, &
programmable logic on page 2–54
.
The Index numbers used for the continuous monitor are as follows:
•
48 – Trip Circuit alarm
•
49 – Zone flags on alarm
•
50 – Overcurrent Alarm
•
51 – Unbalanced Current Detector alarm
They are assigned in the default settings as inputs to the non-critical alarm. These flags may also be used in
configurable logic or assigned to other alarm contacts if required.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...