GE Power Management
LPS-D Line Protection System
B-
25
APPENDIX B
B.1 MEMORY MAPPING
B
R44075I
G3_A10
A10
0 to 256 step 1
R/W
INT
R44076I
G3_A11
A11
0 to 256 step 1
R/W
INT
R44077I
G3_A12
A12
0 to 256 step 1
R/W
INT
R44078I
G3_C1
C1
0 to 256 step 1
R/W
INT
R44079I
G3_C2
C2
0 to 256 step 1
R/W
INT
R44080I
G3_KT1
KT1
0 to 256 step 1
R/W
INT
R44081I
G3_KT2
KT2
0 to 256 step 1
R/W
INT
R44082I
G3_KT3
KT3
0 to 256 step 1
R/W
INT
R44083I
G3_KT4
KT4
0 to 256 step 1
R/W
INT
R44084I
G3_CONFTRIP
CONFTRIP
0 to 256 step 1
R/W
INT
R44085I
G3_CONFOSC
CONFOSC
0 to 256 step 1
R/W
INT
R44100I
G4_Z1PHASE
Z1PHASE
0 = No; 1 = Yes
R/W
INT
R44101F
G4_Z1PHREACH
Z1PHREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R44103F
G4_Z1PLEVDET
Z1PLEVDET
0.0 to 9.9 p.u. V step 0.1
R/W
Float
R44105I
G4_Z1GROUND
Z1GROUND
0 = No; 1 = Yes
R/W
INT
R44106F
G4_Z1GRDREACH
Z1GRDREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R44108I
G4_Z1GRDCHAR
Z1GRDCHAR
0 = Mho; 1 = React
R/W
INT
R44109F
G4_Z1SUREACH
Z1SUREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R44111F
G4_Z1GROUNDK0
Z1GROUNDK0
1.0 to 7.0 step 0.1
R/W
Float
R44113F
G4_Z1GLEVDET
ZIGLEVDET
0.0 to 9.9 p.u. V step 0.1
R/W
Float
R44115I
G4_Z1BLOCK
Z1BLOCK
0 = No; 1 = Yes
R/W
INT
R44116I
G4_Z2PHASE
Z2PHASE
0 = No; 1 = Yes
R/W
INT
R44117F
G4_Z2PHREACH
Z2PHREACH
0.01 to 50.0
Ω
step 0.01 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R44119I
G4_Z2PCHARANG
Z2PCHARANG
90 to 120° step 5
R/W
INT
R44120I
G4_Z2GROUND
Z2GROUND
0 = No; 1 = Yes
R/W
INT
R44121I
G4_Z2GRDCHAR
Z2GRDCHAR
0 = MHO; 1 = GDOC;
2 = MHOGDOC
R/W
INT
R44122F
G4_Z2GRDREACH
Z2GRDREACH
0.01 to 50.0
Ω
step 0.1 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
R44124I
G4_Z2GCHARANG
Z2GCHARANG
90 to 120° step 5
R/W
INT
R44125I
G4_Z2TIMERS
Z2TIMERS
0 = No; 1 = Yes
R/W
INT
R44126F
G4_Z2P_TIME
Z2P_TIME
0.10 to 3.0 sec. step 0.01
R/W
Float
R44128F
G4_Z2G_TIME
Z2G_TIME
0.10 to 3.0 sec. step 0.01
R/W
Float
R44130I
G4_Z3PHASE
Z3PHASE
0 = No; 1 = Yes
R/W
INT
R44131F
G4_Z3PHREACH
Z3PHREACH
0.01 to 50.0
Ω
step 0.1 (5A)
0.05 to 250.0
Ω
step 0.05 (1A)
R/W
Float
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 21 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...