1-
10
LPS-D Line Protection System
GE Power Management
1.3 CUSTOM PROGRAMMABILITY
1 PRODUCT DESCRIPTION
1
1.3 CUSTOM PROGRAMMABILITY
1.3.1 INTRODUCTION
The LPS-D offers a high degree of custom programmability. Custom programming of the LPS-D is accom-
plished using Xpression Builder software. Xpression Builder allows the user to graphically design programma-
ble logic and make I/O (input/output) assignments for the LPS-D and other GE Power Management relays.
Xpression Builder is included with the LPS-D software suite on the GE Power Management CD. A complete
description of Xpression Builder is included in Chapter 13: XPRESSION BUILDER
.
1.3.2 CONFIGURABLE INPUTS
All of the contact converters (Digital Inputs) in the LPS-D are user configurable. However, each LPS-D relay is
shipped with the default contact converter assignments shown in the table below and on Figure 1–22: ELE-
MENTARY DIAGRAM WITH DEFAULT I/O ASSIGNMENTS on page 1–47.
Table 1–3: LPS-D DEFAULT CONTACT CONVERTER ASSIGNMENTS
INPUT
DESCRIPTION
MNEMONIC
INDEX #
NOTE
LPS-D WITH SINGLE PHASE TRIPPING MODELS
CC1
RECEIVER #1
RCVR1
12
CC2
RECEIVER #2
RCVR2
13
(if used)
CC3
EXTERNAL STOP CARRIER
STCR
10
(Blocking Scheme Only)
CC4
BLOCK PILOT TRIPPING
BLPTRP
11
(Blocking Scheme Only)
CC5
ENABLE 3 PHASE TRIPPING
ETRP3P
7
CC6
REMOTE TARGET RESET
RESET
20
CC7
BKR1 52b PHASE A
52B_1A
1
CC8
BKR1 52b PHASE B
52B_1B
2
CC9
BKR1 52b PHASE C
52B_1C
3
CC10
BKR2 52b PHASE A
52B_2A
4
CC11
BKR2 52b PHASE B
52B_2B
5
CC12
BKR2 52b PHASE C
52B_2C
6
LPS-D WITH THREE PHASE TRIPPING MODELS
CC1
RECEIVER #1
RCVR1
12
CC2
RECEIVER #2
RCVR2
13
(if used)
CC3
EXTERNAL STOP CARRIER
STCR
10
(Blocking Scheme Only)
CC4
BLOCK PILOT TRIPPING
BLPTRP
11
(Blocking Scheme Only)
CC5
BKR1 52b
52B_1A
1
CC6
BKR2 52b
52B_2A
4
CC7
REMOTE TARGET RESET
RESET
20
CC8
SPARE
CC9
SPARE
CC10
SPARE
CC11
SPARE
CC12
SPARE
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...