![GE LPS-D Скачать руководство пользователя страница 357](http://html.mh-extra.com/html/ge/lps-d/lps-d_instruction-manual_131861357.webp)
GE Power Management
LPS-D Line Protection System
B-
23
APPENDIX B
B.1 MEMORY MAPPING
B
R43985F
G3_REVREACH
REVREACH
0.1 to 75.0
Ω
step 0.1 (5A)
0.5 to 375.0
Ω
step 0.5 (1A)
R/W
Float
R43987I
G3_OUTER
OUTER
40 to 165° step 1
R/W
INT
R43988I
G3_MIDDLE
MIDDLE
40 to 165° step 1
R/W
INT
R43989I
G3_INNER
INNER
40 to 165° step 1
R/W
INT
R43990I
G3_TLOS1PU
TLOS1PU
1 to 100 msec. step 1
R/W
INT
R43991I
G3_TLOS1DO
TLOS1DO
1 to 100 msec. step 1
R/W
INT
R43992I
G3_TLOS2PU
TLOS2PU
1 to 100 msec. step 1
R/W
INT
R43993I
G3_TLOS3PU
TLOS3PU
1 to 100 msec. step 1
R/W
INT
R43994I
G3_TLOS4PU
TLOS4PU
1 to 100 msec. step 1
R/W
INT
R43995I
G3_RECLMODE
RECLMODE
0 = Off; 1 = None; 2 = Internal;
3 = External; 4 = Both
R/W
INT
R43996I
G3_RECLOSETYPE
RECLOSETYPE
0 = 1POLE; 1 = 3 POLE;
2 = 1POLE3POLE
R/W
INT
R43997I
G3_NUM_1P_AT
NUM_1P_AT
1, 2, 3, 4
R/W
INT
R43998F
G3_1PDELAY1
1PDELAY1
0.1 to 300.0 sec. step 0.1
R/W
Float
R44000F
G3_1PDELAY2
1PDELAY2
0.1 to 300.0 sec. step 0.1
R/W
Float
R44002F
G3_1PDELAY3
1PDELAY3
0.1 to 300.0 sec. step 0.1
R/W
Float
R44004F
G3_1PDELAY4
1PDELAY4
0.1 to 300.0 sec. step 0.1
R/W
Float
R44006I
G3_NUM_3P_AT
NUM_3P_AT
1, 2, 3, 4
R/W
INT
R44007F
G3_3PDELAY1
3PDELAY1
0.1 to 300.0 sec. step 0.1
R/W
Float
R44009F
G3_3PDELAY2
3PDELAY2
0.1 to 300.0 sec. step 0.1
R/W
Float
R44011F
G3_3PDELAY3
3PDELAY3
0.1 to 300.0 sec. step 0.1
R/W
Float
R44013F
G3_3PDELAY4
3PDELAY4
0.1 to 300.0 sec. step 0.1
R/W
Float
R44015F
G3_RESETTIME
RESETTIME
0.1 to 300.0 sec. step 0.1
R/W
Float
R44017F
G3_DWELLTIME
DWELLTIME
0.1 to 2.0 sec. step 0.1
R/W
Float
R44019I
G3_HOLD
HOLD
0 = No; 1 = Yes
R/W
INT
R44020I
G3_HOLDTIME
HOLDTIME
1 to 1000 sec. step 1
R/W
INT
R44021I
G3_HOLDSENSE
HOLDSENSE
0 = CC; 1 = CO
R/W
INT
R44022I
G3_SYNCHCHECK
SYNCHCHECK
0 = No, 1 = Yes
R/W
INT
R44023F
G3_CLOSEANG
CLOSEANG
0 to 75° step 1
R/W
INT
R44025F
G3_SLIPFREQ
SLIPFREQ
0.1 to 5.0 Hz step 0.1
R/W
Float
R44027I
G3_BUSLINE
BUSLINE
0 = BUS; 1 = LINE
R/W
INT
R44028I
G3_SYNCHPHASE
SYNCHPHASE
0 = VA; 1 = VB; 2 = VC
3 = VAB; 4 = VBC; 5 = VCA
R/W
INT
R44029I
G3_SYNCHHOLD
SYNCHHOLD
1 to 100 sec. step 1
R/W
INT
R44030I
G3_SP1DELAY2
SP1DELAY2
1
R/W
INT
R44031I
G3_SP1DELAY3
SP1DELAY3
0 = No; 1 = Yes
R/W
INT
R44032I
G3_SP1DELAY4
SP1DELAYR
0 = No; 1 = Yes
R/W
INT
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 19 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...