![GE LPS-D Скачать руководство пользователя страница 219](http://html.mh-extra.com/html/ge/lps-d/lps-d_instruction-manual_131861219.webp)
GE Power Management
LPS-D Line Protection System
6-
17
6 FUNCTIONAL TESTS (USER SETTINGS)
6.5 ZONE REACH TESTS
6
3.
Choose
øI
(the
I
T
angle).
V
NOM
is at maximum when
øI
=
øZ
– 30°.
øI
1
= [________]° (Zone 1)
øI
2
= [________]° (Zone 2)
øI
3
= [________]° (Zone 3)
øI
4
= [________]° (Zone 4)
4.
Calculate
V
NOM
for each zone by substituting the values of
Z
R
,
øZ
(POSSEQANG),
I
T
, and
øI
into Equa-
tions 25 and 26 for
V
NOM
according to zone.
V
NOM
1
= [________] Volts rms (nominal test voltage for Z1P)
V
NOM
2
= [________] Volts rms (nominal test voltage for Z2P)
V
NOM
3
= [________] Volts rms (nominal test voltage for Z3P)
V
NOM
4
= [________] Volts rms (nominal test voltage for Z4P)
NOTE: If Zone 4 is reversed (Protection Setting 408: Z4DIRECTN = REVERS), remember to add 180° to
both the test current angle,
øI
4
, and the impedance angle,
øZ
4
. If Zone 4 has a non-zero offset, use the
ALPS-Test software to calculate
V
NOM
4
.
5.
Record
V
NOM
n
,
I
T
, and
øI
n
in the space provided in the appropriate Zone reach test.
Table 6–2: TEST CURRENT RANGES FOR PHASE-TO-PHASE REACH
Z
G
Reach
(
I
n
= 5 A)
I
T
(A)
Z
G
Reach
(
I
n
= 1 A)
I
T
(A)
0.1 to 2.5
10
0.5 to 12.5
2
2.5 to 6.0
8
12.5 to 30.0
2
6.0 to 12.0
5
30.0 to 60.0
1
12.0 to 20.0
3
60.0 to 100.0
0.6
20.0 to 30.0
2
100.0 to 150.0
0.4
30.0 to 40.0
1.5
150.0 to 200.0
0.3
40.0 to 50.0
1.0
200.0 to 250.0
0.2
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...