2-
78
LPS-D Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
LINEINFO
1401
P O S S E Q A N G
Positive Sequence Impedance
Angle
25 to 90° step 1
1402
ZERSEQANG
Zero Sequence Impedance
Angle
25 to 90° step 1
1403
ZLINE
Positive Sequence Line
Impedance in sec.ohms
0.01 to 50.0
Ω
step 0.01
0.05 to 250.0
Ω
step 0.05
1404
ZEROSEQK0
Z0/Z1 Ratio
1.0 to 7.0 step 0.1
1405
LINELENGTH
Line Length
0.0 to 500.0 step 0.1
1406
LINEUNIT
Units of Length
MILES, KM
1407
CTRATIO
CT Ratio
1 to 5000 step 1
1408
PTRATIO
PT Ratio
1 to 7000 step 1
SCADA_DATA
1501
F LTL O C K
Hold Time
0 to 99.9 sec. step 0.1
1502
FLTRESET
Fault Location Reset Time
0 to 999 minutes step 1
OS BLOCKING
1601
M O B ZO N E
Coordinating Zone
ZONE2, ZONE3, ZONE4
1602
M O B C H A R A N G
MOB Characteristic Angle
30 to 130° step 1
1603
BLOCKWHAT
Block during OS
BLKALL, BLKDIST, BLKPHAS, BLKNONE
1604
BLOCKZ1
Block all Zone 1 Functions
NO, YES
1605
BLOCKZ2
Block all Zone 2 Functions
NO, YES
1606
BLOCKZ3
Block all Zone 3 Functions
NO, YES
1607
BLOCKZ4
Block all Zone 4 Functions
NO, YES
RECLOSER
1801
R E C LM O D E
Select Reclosing Option
OFF, NONE, INTERNAL, EXTERNAL,
BOTH
1802
RECTYPE
Set Reclosing Type
1POLE, 3POLE, 1POLE/3POLE
1803
NUM1P
Number of Attempts Following
1P Trip
1 to 4 step 1
1804
1PDELAY1
1 Pole First Delay
0.1 to 300 sec. step 0.1
1805
1PDELAY2
1 Pole Second Delay
0.1 to 300 sec. step 0.1
1806
1PDELAY3
1 Pole Third Delay
0.1 to 300 sec. step 0.1
Table 2–10: PROTECTION SETTINGS DATA SHEET (Sheet 6 of 9)
No.
M nem onic
Description
Range (5A)
Range (1A)
User Setting
†
Setting value QUAD applies to LPS-D Revision B models only.
‡
Setting is applicable to Revision B models only.
^
Setting is applicable to LPS-D models with three phase tripping only.
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...