B-
22
LPS-D Line Protection System
GE Power Management
B.1 MEMORY MAPPING
APPENDIX B
B
R43945I
G3_TRIPMODE
TRIPMODE
0 = 3POLE; 1 = 1POLE;
2 = 1POLEZ2
R/W
INT
R43946I
G3_CARRSTART
CARRSTART
0 = DIR; 1 = IPB; 2 = FD
R/W
INT
R43947I
G3_WKINFTRIP
WKINFTRIP
0 = No; 1= Yes
R/W
INT
R43948I
G3_TL1PICKUP
TL1PICKUP
1 to 200 msec. step 1
R/W
INT
R43949I
G3_TL4PICKUP
TL4PICKUP
0 to 50 msec. step 1
R/W
INT
R43950I
G3_TL4DROPOUT
TL4DROPOUT
0 to 50 msec. step 1
R/W
INT
R43951I
G3_TL5PICKUP
TL5PICKUP
0 to 200 msec. step 1
R/W
INT
R43952I
G3_TL5DROPOUT
TL5DROPOUT
0 to 200 msec. step 1
R/W
INT
R43953I
G3_TL6PICKUP
TL6PICKUP
0 to 200 msec. step 1
R/W
INT
R43954I
G3_TL6DROPOUT
TL6DROPOUT
0 to 200 msec. step 1
R/W
INT
R43955I
G3_TL16PICKUP
TL16PICKUP
8 to 99 msec. step 1
R/W
INT
R43956I
G3_TL24DROPOUT
TL24DROPOUT
30 to 500 msec. step 1
R/W
INT
R43957I
G3_TL25DROPOUT
TL25DROPOUT
30 to 500 msec. step 1
R/W
INT
R43958I
G3_TL26PICKUP
TL26PICKUP
0 to 50 msec. step 1
R/W
INT
R43959I
G3_POSSEQANG
POSSEQANG
25 to 90° step 1
R/W
INT
R43960I
G3_ZERSEQANG
ZERSEQANG
25 to 90° step 1
R/W
INT
R43961F
G3_ZLINE
ZLINE
0.01 to 50
Ω
step 0.01
0.05 to 250
Ω
step 0.05
R/W
Float
R43963F
G3_ZEROSEQK0
G3_ZEROSEQK0
1.0 to 7.0 step 0.1
R/W
Float
R43965F
G3_LINELENGTH
LINELENGTH
0.0 to 500.0 step 0.1
R/W
Float
R43967I
G3_LINEUNIT
LINEUNIT
0 = Miles, 1 = Km
R/W
INT
R43968I
G3_CTRATIO
CTRATIO
1 to 5000 step 1
R/W
INT
R43969I
G3_PTRATIO
PTRATIO
1 to 7000 step 1
R/W
INT
R43970F
G3_FLTLOCK
FLTLOCK
0 to 99.9 sec. step 0.1
R/W
Float
R43972I
G3_FLTRESET
FLTRESET
0 to 999 minutes step 1
R/W
INT
R43973I
G3_MOBZONE
MOBZONE
0 = Zone 2; 1 = Zone 3;
2 = Zone 4
R/W
INT
R43974I
G3_MOBCHARANG
MOBCHARANG
30 to 130° step 1
R/W
INT
R43975I
G3_BLOCKWHAT
BLOCKWHAT
0 = BLKALL; 1 = BLKDIST;
2 = BLKPHAS; 3 = BLKNONE
R/W
INT
R43976I
G3_BLOCKZ1
BLOCKZ1
0 = No; 1 = Yes
R/W
INT
R43977I
G3_BLOCKZ2
BLOCKZ2
0 = No; 1 = Yes
R/W
INT
R43978I
G3_BLOCKZ3
BLOCKZ3
0 = No; 1 = Yes
R/W
INT
R43979I
G3_BLOCKZ4
BLOCKZ4
0 = No; 1 = Yes
R/W
INT
R43980I
G3_USE_OST
USE_OST
0 = No; 1 = Yes
R/W
INT
R43981I
G3_NUMBRCHAR
NUMBRCHAR
2, 3
R/W
INT
R43982I
G3_TRIPIN_OUT
TRIPIN_OUT
0 = IN; 1 = OUT
R/W
INT
R43983F
G3_FWDREACH
FWDREACH
0.1 to 75.0
Ω
step 0.1 (5A)
0.5 to 375.0
Ω
step 0.5 (1A)
R/W
Float
Table B–4: MODBUS MEMORY MAP: SETPOINTS
(Sheet 18 of 27)
Register
Address
DDE Item Name
(Mnemonic)
Contents
Units/Value/Range
R/W
Format
Code
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...