5 FUNCTIONAL TESTS (FACTORY SETTINGS)
5.2 MEASURING UNIT TESTS
5
5.2.6 T6 – PHASE INSTANTANEOUS OVERCURRENT 50
1.
Protection settings:
OVERCURRNT
(601)
50 = YES
(602)
50_DIRCNL = NO
(603)
50PICKUP = 5.0 (1.0)
2.
Connect the relay as shown in Figure 5–1: PHASE-TO-PHASE TEST CONNECTIONS on page 5–7 for a
phase AB, BC, or CA fault. Note that the leading phase is 180 degrees out of Phase with the line to which
it is shorted.
3.
Set the relay into test mode 43 (Phase Overcurrent). The LUI should display
INST PHS OVRC ON
4.
Set
I
op
to 2.8 (0.6) A rms and apply to the relay. The A1 contact should close. Lower
I
op
to 2.0 (0.4) A rms,
at which point the A1 contact should open.
5.
Reduce
I
op
to 0 A.
6.
Restore the following Protection settings
OVERCUR
(602)
50_DIRCNL = YES
(603)
50PICKUP = 20.0 (4.0) Amps
5.2.7 T7 – GROUND INSTANTANEOUS OVERCURRENT 50G
1.
Protection settings:
OVERCURRNT
(605)
50G = YES
(606)
50G_DIRCNL = NO (Directnl ctrl off)
(607)
50GPICKUP = 2.5 (0.5) Amps
(608)
50GRESTNT = 0
2.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS on page 4–14.
3.
Set the relay into test mode 44 (Ground Overcurrent). The LUI displays
INST GND OVRC ON
4.
Set
I
op
to 4.0 (0.80) A rms and apply to the relay. The A1 contact should close. Lower
I
op
to 2.4 (0.40) A
rms, at which point the A1 contact should open.
5.
Reduce
I
op
to zero.
6.
Restore the following settings
OVERCURRNT
(605)
50G_DIRCNL = YES
(605)
50GPICKUP = 10 (2.0) Amps
Содержание LPS-D
Страница 2: ......
Страница 4: ......
Страница 164: ...3 14 LPS D Line Protection System GE Power Management 3 3 PRINTED CIRCUIT BOARD MODULES 3 HARDWARE DESCRIPTION 3 ...
Страница 226: ...7 4 LPS D Line Protection System GE Power Management 7 1 RATINGS 7 SPECIFICATIONS 7 ...
Страница 284: ...10 20 LPS D Line Protection System GE Power Management 10 8 HELP MENU 10 ALPS TEST PROGRAM 10 ...
Страница 334: ...A 4 LPS D Line Protection System GE Power Management A 1 FREQUENTLY ASKED QUESTIONS APPENDIXA A ...
Страница 412: ...C 34 LPS D Line Protection System GE Power Management C 3 POINT LISTS APPENDIXC C ...
Страница 416: ...D 4 LPS D Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 422: ...F 2 LPS D Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 435: ...GE Power Management LPS D Line Protection System xiii INDEX INDEX tests 6 11 ZONE TIMER functional tests 5 10 ...
Страница 436: ...xiv LPS D Line Protection System GE Power Management INDEX INDEX ...